Daylight Harvesting Applications

9

Daylight Harvesting Applications

Based on the ambient light level in the space, the controller modulates light intensity from
lighting fixtures on the primary and secondary daylighting channels, Channel 1 and 2
respectively. The daylight harvesting application does not affect the relay operation.

When daylighting is active and is driving the two outputs, a switch, gateway command or
occupancy sensor cannot force the light level higher. However, a switch, occupancy sensor, or
gateway command can override the light OFF or dim to a level below the daylighting control
value.

The fixtures closest to the natural light source must be connected to Channel 1, the primary
daylighting channel. If the space has a secondary daylighting zone, the fixtures in the zone
must be connected to Channel 2, the secondary daylighting channel. Channel 3 does not
perform any daylighting routine.

Note:

The controller only supports one linked photo sensor.

Daylight harvesting does not affect the operation of wall switches or occupancy sensors when
the light is ON. If the light is ON, either a switch or occupancy sensor can override with an OFF
action or dim to below the daylighting control value. See

Photo Inhibit on page 1

.

Daylighting Control Override

The open or closed loop daylighting features can be temporarily overridden by enabling the

daylighting manual override

parameter. The override has a timer that releases the override

once expired and daylighting control resumes.

If the override is enabled, a switch can turn lights ON and manually set the dimming level.

Garibaldi Pro software is required to configure both the

daylighting manual override timer

and

daylighting manual override enable

parameters.

Closed Loop Control

Closed loop daylighting becomes active when a photo sensor with a maximum detectable
range of light less than 2500 lux is linked to the controller. In closed loop daylighting, the
sensor indirectly monitors the controlled light output from the fixtures plus some of the
natural light contribution.

When the lights are on, closed loop daylighting tries to maintain a given set point level within
the space. This level is specified in the

closed loop daylighting set point

parameter. The

controller only adjusts the dimming output on received photo sensor messages and only when
the light is ON. If the light is OFF, closed loop daylighting is ignored.

To set the

closed loop daylighting set point

using Simple Tap, a photo sensor with monitoring

range less than 2500 lux and a switch must be linked to the controller.

Note:

This process is best performed when there is little or no natural light; either

close the blinds or complete this step at night.

1. Turn the light ON.
2. Use a handheld photometer to measure the light on the task plane and press the fixture's

switch to adjust its light level until it matches the target light level.

Содержание Echoflex ELED3

Страница 1: ...Part Number 8189M2410 Rev A Released 2022 10 Tri Zone Dimming Controller Models ELED3 and ELED3H Configuration Guide...

Страница 2: ...marks and patents go to echoflexsolutions com ip All other trademarks both marked and not marked are the property of their respective owners Echoflex intends this document whether printed or electroni...

Страница 3: ...nction 3 Status Message 4 Radio Range Confirmation 4 Dimming Outputs 4 Near Cross Technology 4 Switch Operation 5 Timed Switches 5 Occupancy Based Lighting Applications 5 Occupancy Sensor Auto OFF Tim...

Страница 4: ...Open Loop Control 10 Controller Presets 11 User Interface 12 Power LED and Learn LED 12 Learn Button 12 Remote Linking Solution 13 Clear Button 13 LED Display 13 Blink Indications 14 Device Count Cod...

Страница 5: ...rimary channel by the offset value providing consistent dimming results across the space as the natural light changes The third dimming channel can be controlled by linked occupancy sensors switches o...

Страница 6: ...ng statement indicates situations where damage may occur people may be harmed or there are serious or dangerous consequences of an action WARNING RISK OF ELECTRIC SHOCK This warning statement indicate...

Страница 7: ...ly use your finger to activate the sensors and switches linked to the controller The tap in Simple Tap means a quick press on a sensor s Teach button and or a switch s ON OFF If the sensor is linked t...

Страница 8: ...s vicinity must be disabled The controller receives a unique message from the sensor evaluates the signal strength and sends back a unique message containing the strongest signal value received The s...

Страница 9: ...r for the configured period One minute before the timer expires and the lights turn off the lights blink once as a warning Flick Warn Switching the lights ON at anytime resets the timer Switching the...

Страница 10: ...an undetected occupant to signal that the space is occupied Garibaldi Pro software is required to configure the grace timer The default is 30 seconds Dual Technology Occupancy Sensors Dual Tech senso...

Страница 11: ...s the ideal tool to set up your project and configure settings or even to make edits if your project has been pre commissioned Garibaldi Pro is available for download at echoflexsolutions com There is...

Страница 12: ...e vacancy fade OFF rate if other than the default two seconds is required Hospitality Applications Hospitality is a specific kind of occupancy based control When the controller is used in a hotel or d...

Страница 13: ...dden by enabling the daylighting manual override parameter The override has a timer that releases the override once expired and daylighting control resumes If the override is enabled a switch can turn...

Страница 14: ...ghting set point Garibaldi Pro software is required to configure both the amount of change per message and the dead band value parameters Open Loop Control Open loop daylighting becomes active when a...

Страница 15: ...1000 lux Taps Max Output Set point Min Output Set point Light Response 0 tap 5 30 1 blink 1 tap 10 35 2 blinks 2 taps 15 40 3 blinks 3 taps 20 50 4 blinks 4 taps 25 55 5 blinks Controller Presets Pres...

Страница 16: ...primary daylighting with set point Green Channel 2 secondary daylighting with offset from set point Blue Channel 3 occupancy sensors switches or gateway commands No photo sensor non daylighting Learn...

Страница 17: ...ton can be used to reset the controller either to its pre commissioned state or to its factory default state To reset to pre commissioned state 1 Press and hold the Clear button until the red Power an...

Страница 18: ...hat count the sensors Off Photo sensor maximum of 1 3 long blinks followed by short blink that counts the sensor Off Gateways and TimeClocks 4 long blinks followed by short blinks that count the devic...

Страница 19: ...radio communications Any modifications or changes to this product not expressly approved by Electronic Theatre Controls Inc could void the user s authority to operate the product Operation of this eq...

Страница 20: ...16 Tri Zone Dimming Controller Configuration Guide...

Страница 21: ...Compliance 17...

Страница 22: ...18 Tri Zone Dimming Controller Configuration Guide...

Страница 23: ...Compliance 19...

Страница 24: ...o echoflexsolutions com Support service echoflexsolutions com 2022 Echoflex Solutions Inc Trademark and patent info echoflexsolutions com ip Product information and specifications subject to change Ec...

Отзывы: