D4 Series Drivers Installation Guide
Wall-Mount Emergency Driver Installation
CAUTION:
RISK OF SHOCK AND FIRE - This unit has more than one power
supply connection point. To reduce the risk of electric shock disconnect both
the branch circuit-breakers or fuses and emergency power supplies before
servicing.
ATTENTION :
RISQUE D'INCENDIE ET DE CHOC - Cet appareil posséde
plusieurs points de connexion d'alimentation. Pour réduire le risque de choc
électrique déconnecter les disjoncteurs de dérivation ou les fusibles et les
alimentations de secours avantl'entretien.
CAUTION:
Service by qualified personnel only. De-energize before opening.
ATTENTION :
Service par du personnel qualifié uniquttes. Hors tension
avant d'ouvrir.
With the exception of power input terminations, Wall-Mount D4 Emergency Driver installation
requirements are the same as those of the standard Wall-Mount D4 Driver. Complete the
installation as follows, referencing these sections for installation details:
•
Review
Prepare for Wall-Mount Installation on page 17
•
Review
Electrical and Wiring Specification on page 15
•
Complete
Wall-Mount the Driver on page 17
•
Complete
Terminate Normal Sense Input on the facing page
•
Complete
Terminate Maintained (Emergency) Input on page 36
•
Complete
•
Complete
DMX In and DMX Thru on page 23
After completing D4 Emergency Driver installation, see
Final Installation and Operation on
Note:
Normal and emergency wiring cannot be contained in the same conduit
according to NEC 700.10(B).
Note:
Use suitable conduit where required by local or national code.