background image

E T C   I n s t a l l a t i o n   G u i d e

Automatic Load Control Relay

Automatic Load Control Relay

 Page 1 of 8

Electronic Theatre Controls, Inc.

Corporate Headquarters

 

 3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA 

 Tel +608 831 4116 

 Fax +608 836 1736

London, UK

 

 Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK 

 Tel +44 (0)20 8896 1000 

 Fax +44 (0)20 8896 2000

Rome, IT 

 

Via Pieve Torina, 48, 00156 Rome, Italy 

 Tel +39 (06) 32 111 683 

 Fax +44 (0)20 8752 8486

Holzkirchen, DE

 

 Ohmstrasse 3, 83607 Holzkirchen, Germany 

 Tel +49 (80 24) 47 00-0 

 Fax +49 (80 24) 47 00-3 00

Hong Kong 

 Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong 

 Tel +852 2799 1220

Service: 

(Americas)

 [email protected]

 

 

(UK)

 [email protected]

 

 (DE)

 [email protected]

 

 

(Asia)

 [email protected]

Web:

 www.etcconnect.com

 

 Copyright © 2014 ETC. All Rights Reserved. 

 Product information and specifications subject to change.

7180M2150

 

 Rev G 

 Released 2014-07 

 ETC intends this document to be provided in its entirety.

Overview

The Automatic Load Control Relay (ALCR) is a UL 924 listed device that is powered 
from an emergency source and provides power to emergency lighting load(s). The 
ALCR ensures a “lights on state” during loss of normal power while tracking the state of 
normal lighting loads during normal operation. The ALCR also assures a “lights on” 
override by utilizing a normally closed emergency contact closure which interfaces with 
fire alarm and emergency systems.

The ALCR is available in two models for installation convenience including Power Pack 
(ALCR-PP) and DIN-rail (ALCR-DIN).

Electrical Specifications

Rated for indoor use only. UL, cUL listed Emergency Lighting and Power under 
UL 924 at line voltages of 120 and 277 VAC, 60 Hz.

• Load ratings include:

• Ballast loads, 20A maximum at 120 or 277 VAC
• Incandescent loads - 10A maximum at 120 or 277 VAC

• Provides remote activation by dry contact closure for connection to a fire alarm or 

building management system.

• ALCR-DIN model only provides auxiliary contact for 0-10 Vdc/ Fluorescent ballasts.

WARNING:

Risk of electric shock! The ALCR utilizes high voltage and should only be 
installed by a qualified installer or electrician. Follow all local codes for 
installation and follow the proper lockout/tag out procedures per NFPA 
Standard 70E.

ALCR-PP

ALCR-DIN

Содержание ALCR-DIN

Страница 1: ...rol Relay ALCR is a UL 924 listed device that is powered from an emergency source and provides power to emergency lighting load s The ALCR ensures a lights on state during loss of normal power while t...

Страница 2: ...DIN rail 35mm complies with DIN43880 and EN60715 Reference Installation and Termination of the ALCR DIN on page 4 Once installation of the Automatic Load Control Relay is complete reference Configurat...

Страница 3: ...s to the normal lighting circuit as shown b Connect the Normal Neutral White 18 AWG lead to the normal Neutral for the lighting loads Step 6 Proceed to Initial Test on page 7 Step 7 If you are install...

Страница 4: ...single pole contacts on the remote device or test switch Step 3 Continue to Remote Activation Test on page 7 Installation and Termination of the ALCR DIN The ALCR DIN is designed to attach to lighting...

Страница 5: ...ch Sense and Normal Neutral screw terminals as shown Step 4 If you are connecting to 0 10 Vdc Fluorescent lighting loads connect to the provided terminals labeled 0 10V FLO Reference Examples of Use o...

Страница 6: ...a user configurable delay time between regaining normal power and removing power from the emergency lighting This delay time could be used to account for loads that may require a warm up time for exam...

Страница 7: ...f reconnect the Normal Power Switch wire to the terminal Step 6 Turn On the normal circuit breaker The ALCR should now behave as described in the Examples of Use on page 8 Step 7 If you are installing...

Страница 8: ...gency Light Fixture ALCR Normal Neutral White Normal Hot Black Emergency Load Emergency Hot Emergency Neutral Gray Backup Arrangement When normal power is present the emergency load is turned off When...

Отзывы: