Electrical connection
HE-C3 board
25
10.1
HE-C3 board
Terminal
Function
Default assignment
S1
CAN-Bus node switch
F25
Fuse 230 V, T 8A ([S66]: [L2])
F27
Fuse 230 V, T 8A ([S66]. [L1])
F29
Fuse 230 V, T 8A ([S66].: [L3])
F31
Fuse 230 V, T 630 mA
([S68], [S69])
S65
Supply 400 V
Supply cable 2.5² (via contactor)
S66
400 V output
Drive motor for conveyor screw in fuel store (via
contactor)
S68
230 V output
Drive motor for pellet flap
S69
230 V output
Aspirator (via contactor)
S560
CAN-Bus
to boiler
S562
24 V input
Pellet bin fill level sensor
S563
24 V input
Pellet flap end position sensor
S564
24 V input
Drop chute fill level sensor
S565
24 V input
Aspirators drive protection
X2
CAN-bus terminator resistor
Wall housing
terminal
Function
Default assignment
X1 - 1
Series terminal
Emergency stop switch (from circuit board
[HA-C]: terminal [S52]: contact [NC])
X1 - 2
Series terminal
Emergency stop switch
(from circuit board [HA-
C]: terminal [S51]: contact [N])
Terminals marked with this symbol are not pre-wired.