9.2.6  Diagnostic data for one channel

The dynamic information for one channel consists of 22 bytes.
Access: Index number of channel, subindex 6
All dynamic information with possible conditions is described in the following table.

byte

type

range

description

Error memory

0 HighByte
1 LowByte

UInt16 0 ... 65535

bit 0 = no parameters available
bit 1 = error parameter memory
bit 2 = error programme memory
bit 3 = error data memory
bit 4 = error control unit
bit 5 = reset through watchdog
bit 6 = reserve
bit 7 = reserve
bit 8 = reserve
bit 9 = reserve
bit 10 = reserve
bit 11 = reserve
bit 12 = reserve
bit 13 = reserve
bit 14 = reserve
bit 15 = reserve
»True« means the status is active.

Trip counter

2 HighByte
3 LowByte

UInt16 0 ... 65535

The number of trippings since the last reset of is shown here.

Reason for trip

4

byte

0 ... 255

0 = no trip
1 = short circuit
2 = overload
3 = device temperature too high
4 = internal device failure

Min. 
Load voltage

5 HighByte
6 LowByte

UInt16 0 ... 65535

Contains the highest measured voltage of the channel since 
the last reset.
A standardised 16-bit-value with a resolution of 10 mV is made 
available.
Example for calculation of the measuring value:
value (2512)/100 =^25.12 Volt

Max. 
Load voltage

7 HighByte
8 LowByte

UInt16 0 ... 65535

Contains the highest measured voltage of the channel since 
the last reset.
A standardised 16-bit-value with a resolution of 10 mV is made 
available.
Example for calculation of the measuring value:
value (2512)/100 =^25.12 Volt

Medium value
Load voltage

9 HighByte
10 LowByte

UInt16 0 ... 65535

Contains the mean voltage value of the channel since the last 
reset.
A standardised 16-bit-value with a resolution of 10 mV is made 
available.
Example for calculation of the measuring value:
value (2512)/100 =^25.12 Volt

Min. load current

11 HighByte
12 LowByte

UInt16 0 ... 65535

Contains the lowest measured current of the channel since the 
last reset.
A standardised 16-bit-value with a resolution of 10 mA is 
made available.
Example for calculation of the measuring value:
value (150)/100 =^1.50 Amps

Содержание ControlPlex CPC12EC

Страница 1: ...User Manual ControlPlex Controller CPC12EC ...

Страница 2: ...3 3 4 LED status indication 9 4 Mounting and installation 9 4 1 Mounting of the system 9 5 Operating modes of the CPC12 bus controller 10 5 1 Operating mode Start up mode 10 5 2 Operating mode System error mode 10 5 3 Operating mode Configuration error mode 10 5 4 Operating mode Stand alone mode 10 5 5 Operating mode Slave mode 10 5 5 Operating mode Firmware Update Mode 10 6 Basic functions of the...

Страница 3: ...data 19 9 1 CPC12 controller 20 9 1 1 Device information CPC12 controller 20 9 1 2 Configuration data CPC12 controller 21 9 1 3 Action commands CPC12 controller 22 9 1 4 Dynamic information CPC12 controller 23 9 2 Circuit protectors channels 23 9 2 1 Device parameters for one channel 23 9 2 2 Device information for one channel 24 9 2 3 Configuration data for one channel 25 9 2 4 Event message for ...

Страница 4: ... Qualified personnel This user manual must exclusively be used by qualified personnel who are able based on their training and experience to realise arising problems when handling the product and to avoid related hazards These persons have to ensure that the use of the product described here meets the safety requirements as well as the requirements of the presently valid directives standards and l...

Страница 5: ...ch are connected with each other via an integral connector arm without requiring additional components Power supply is via the EM12 supply module which can supply the circuit protectors with max 40 A The new CPC12 bus controller additionally allows access to all system relevant data of the superordinate control systems This can be via the the EtherCAT interface as well as via an additional Etherne...

Страница 6: ...es and status information independently of the control system e g to a superordinate cloud application Revised measuring values of all electronic circuit protectors are also forwarded to the automation system This enables the user to have unrestricted access to the safety relevant functions even in the event of an interruption Any occurring failures will be detected quickly and can be remedied wit...

Страница 7: ...sure space for plugs and cables Label e g from Phoenix Contact ZBF 21 connector arm X1 Ethernet interface XF1 IN EtherCAT interface XF2 OUT EtherCAT interface XD1 DC24 V XD1 0 V XD1 FE IP Reset LED LINK ACT LED LINK ACT LED LINK ACT XD1 supply terminal LED US1 LED US2 LED ERR LED RUN fig 2 Dimensions CPC12 fig 3 Status indication and terminals CPC12EC ...

Страница 8: ...cond after applying the supply voltage of the circuit protectors Otherwise the circuit protectors will work in the stand alone mode i e wihtout internal communication between circuit protectors and bus controller 3 3 2 EtherCAT interfaces with integral switch connection sleeve XF1 IN XF2 OUT XF1 Connection to bus system EtherCAT Type RJ45 When wiring and connecting to the EtherCAT bus system the i...

Страница 9: ...e off off off off No actuator voltage n a red n a n a No connected device or bus error n a orange blinking 0 5 s on 0 5 s off n a n a 3 3 4 LED status indication Visual status indication by means of multicoloured LED Visual signalling of RJ45 interfaces LED LINK ACT Operating mode Indication of operating mode Link available green No link available off Act available green blinking 4 Mounting and in...

Страница 10: ... protectors their status and parameters can be accessed via the Ethernet interface interface It is thus possible to change e g parameter data of the various electronic circuit protectors After connection is built up to the superordinate control unit this operating mode will be left and the control unit will take over control again as master If during this time a parameter was changed while there w...

Страница 11: ...rised with the available parameters for address slot Transmission of the parameters will be without interruption of the cyclical data exchange between the CPC and the electronic circuit protector 6 3 About the additional Ethernet interface The additional Ethernet interface extends the functional scope of the bus controller The following functionalities are provided via this interface 6 3 1 Web Ser...

Страница 12: ...er 2 Product Code r 4 byte integer 3 Revision Number r 4 byte integer 4 Serial Number r 4 byte integer 0x1600 Channel Control PDO 0 Number of Entries r 1 byte integer 1 Output Mapping Area 1 r 4 byte integer 2 Output Mapping Area 2 r 4 byte integer 3 Output Mapping Area 3 r 4 byte integer 4 Output Mapping Area 4 r 4 byte integer 0x1A00 Channel status PDO 0 Number of Entries r 1 byte integer 1 Inpu...

Страница 13: ...teger 1 Subindex 001 r 1 byte integer 2 Subindex 002 r 1 byte integer 3 Subindex 003 r 1 byte integer 4 Subindex 004 r 1 byte integer 0x1C12 Sync Manager 2 PDO Assignment 0 Number of Entries r 1 byte integer 1 Subindex 001 r 1 byte integer 0x1C13 Sync Manager 3 PDO Assignment integer 0 Number of Entries r 1 byte integer 1 Subindex 001 r 1 byte integer 2 Subindex 002 r 1 byte integer 3 Subindex 003...

Страница 14: ... Information r 19 byte integer 3 Device Type Config rw 2 byte integer 4 Events r 1 byte integer 5 Action Commands Channel w 1 byte integer 6 Dynamic Information r 22 byte integer 0x2120 Acyclic Data CH32 0 Number of Entries r 1 byte integer 1 Parameter Channel rw 2 byte integer 2 Device Information r 19 byte integer 3 Device Type Config rw 2 byte integer 4 Events r 1 byte integer 5 Action Commands...

Страница 15: ...nnel Control 0 Number of Entries r 1 byte integer 1 1 1 Status w 2 byte integer 2 1 2 Status w 2 byte integer 3 2 1 Status w 2 byte integer 32 16 2 Status w 2 byte integer 0xF000 Modular Device Profile 0 Number of Entries r 1 byte integer 1 Module Index Distance r 2 byte integer 2 Maximum Number of Profiles r 2 byte integer 0xF030 Configured Module List 0 Number of Entries r 1 byte integer 1 Subin...

Страница 16: ... later system extensions and which cannot currently be used 8 1 2 Total current CPC12 controller Register 0xF120 subindex 1 contains the total current A 16 bit value with the calculated total current of all circuit protectors entered in the slot 2 bytes input data is made available The sub module does not have output data The measuring value is indicated as follows byte type range description Stat...

Страница 17: ...ice configured bit 0 load output ON bit 1 short circuit bit 2 overload bit 3 low voltage bit 4 reserve bit 5 reserve bit 6 limit value current bit 7 event True means the status is active Load current channel 1 1 HighByte 2 LowByte UInt16 0 65535 A standardised 16 bit value with a resolution of 10 mA is made available Example for calculation of the measuring value value 150 100 1 50 Amps Load volta...

Страница 18: ... range description Control channel 1 0 byte 0 255 bit 0 load output ON OFF bit 1 reset load output only responds to rising edge 0 1 bit 2 reserve bit 3 reserve bit 4 reserve bit 5 reserve bit 6 reserve bit 7 reserve True means the status is active Control channel 2 1 byte 0 255 bit 0 load output ON OFF bit 1 reset load output only responds to rising edge 0 1 bit 2 reserve bit 3 reserve bit 4 reser...

Страница 19: ...see chapter 9 1 1 0x2100 02 5 R W configuration data of CPC12 controller see chapter 9 1 2 0x2100 01 1 W action commands for all channels and the CPC12 controller see chapter 9 1 3 0x2100 04 4 R dynamic information of CPC12 controller see chapter 9 1 4 Index Subindex Number of data bytes Reading R Writing W Description 0x2100 number of channel 01 2 R W Device parameters of a channel see chapter 9 ...

Страница 20: ...nstalled product Serial number 12 HwHb 13 HwLB 14 LwHB 15 LwLB UInt32 0 4294967295 holds the serial number of the installed product Software version major x x 16 byte 0 255 holds the major software version of the installed product Software version x minor x 17 byte 0 255 holds the minor software version of the installed product Software version x x build 18 byte 0 255 holds the build software vers...

Страница 21: ... the LEDs will be dimmed for power reduction bit 3 reserve bit 4 reserve bit 5 reserve bit 6 reserve bit 7 reserve If not described otherwise True means that the function is active Control commands disable ELBus 1 on CPC channel 1 16 1 HighByte 2 LowByte UInt16 0 65535 Each bit represents a channel bit 0 channel 1 bit1 channel 2 If the bit is set this means that the channel cannot be switched on o...

Страница 22: ...led by the PLC not the configured device types not the statistical values min max avg of the channels not the error memory trip counter and trip reason of the channels configuration data power saving mode False LEDs normal behaviour of load outputs in the event of field bus interruption True status is preserved writing via webserver allowed True 2 The command 131 back to box within the action comm...

Страница 23: ...s 1 0 HighByte 1 LowByte UInt16 0 65535 Holds the internal cycle time of the ELBus in milliseconds ms Reserve 2 HighByte 3 LowByte UInt16 0 65535 reserve fig 18 Device parameters channel byte type range description Rated current 0 byte 1 25 Holds the current rating of the channel With adjustable devices you can set a new current rating here and transmit with a write command 1 1A current rating 2 2...

Страница 24: ...95 holds the production facilities number of the installed product Serial number 12 HwHb 13 HwLB 14 LwHB 15 LwLB UInt32 0 4294967295 holds the serial number of the installed product Software version major x x 16 byte 0 255 holds the major software version of the installed product Software version x minor x 17 byte 0 255 holds the minor software version of the installed product Software version x x...

Страница 25: ...Circuit breaker p n 0 HighByte 1 LowByte UInt16 0 65535 The expected device type is adjusted here for the channel The device type always influences a circuit protector i e both possible channels 36873 REX12D TA1 36874 REX12D TA2 36878 REX12D TE2 36906 REX12D TA2 CL2 36910 REX12D TE2 CL2 This list may be extended by future circuit protectors byte type range description Event 0 byte 0 255 bit 0 wait...

Страница 26: ...ax avg of the channels not the error memory trip counter and trip reason of the channels 2 The command 131 back to box within the action commands per channel shall reset the following data Parameters rated current 10 A limit value load current 80 of each channel PLC lock bit of each channel default True i e channel not controllable by PLC configured device types default REX12D TA1 0x9009 36873 the...

Страница 27: ...in Load voltage 5 HighByte 6 LowByte UInt16 0 65535 Contains the highest measured voltage of the channel since the last reset A standardised 16 bit value with a resolution of 10 mV is made available Example for calculation of the measuring value value 2512 100 25 12 Volt Max Load voltage 7 HighByte 8 LowByte UInt16 0 65535 Contains the highest measured voltage of the channel since the last reset A...

Страница 28: ...6 0 65535 Holds the supply voltage actuator voltage of the channel A standardised 16 bit value with a resolution of 10 mV is made available Example for calculation of the measuring value value 2512 100 25 12 Volt Reserve 19 HighByte 20 LowByte UInt16 0 65535 reserve Diagnostic information of the channel 21 byte 0 255 0 OK 1 available device type does not match the configured type 2 no device detec...

Страница 29: ...iagnostic data CPC12 16 fig 9 Total current 16 fig 10 Input data circuit protector 17 fig 11 Output data circuit protector 18 fig 12 Division of parameter index CPC12 19 fig 13 Division of parameter index channel 19 fig 14 Device information CPC12 20 fig 15 Configuration data CPC12 21 fig 16 Action commands CPC12 22 fig 17 Dynamic information CPC12 23 fig 18 Device parameters channel 23 fig 19 Dev...

Страница 30: ...30 Notes ...

Страница 31: ...31 Notes ...

Страница 32: ...RMANY Phone 49 9187 10 0 Fax 49 9187 10 397 E mail info e t a de www e t a de Bedienungsanleitung Instruction manual B_CPC12EC Tx xxx_E_12082020 Bestell Nr Ref number Y31350801 Index a Ausgabe Issue 08 2020 Alle Rechte vorbehalten All rights reserved http www e t a de qr1043 ...

Отзывы: