38
www.eta.co.at
[BufferFlex] function block
ETAtouch controller
Explanation of [Min. out. temp. Solar prio.]
This parameter sets the minimum value for the outside
temperature, so that one of the conditions for solar
priority and stratified charging of the buffer storage
tank is satisfied.
Explanation of [Extra solar heat]
This parameter indicates whether the buffer is transfer-
ring the excess heat from the solar heating system to
the consumers, even if they currently do not need heat.
With the [No] display, the buffer will not transfer any
excess solar heat. If [Yes] is displayed, excess so-
lar heat is forwarded.
The following conditions must be met in order for
the excess solar heat to be passed on in this way:
•
The current outside temperature must be higher
than the adjustable value [from outside temp.].
•
In the function block for the hot water tank, heating
circuits or other buffer storage tanks, the [Solar
heat diss.] parameter must be set to [Yes].
•
The following temperatures must be exceeded in
the buffer:
–If the [Buffer] function block is configured, the
[Buffer top] temperature must be above the
configurable value [at buffer top] and the
[Buffer bottom Solar] temperature above the
value [at buffer bottom sol.].
–If the function block
[BufferFlex]
is
configured, the temperature [from accumulator
tank temperature] at
the
allocated
tempera-
ture sensor must be exceeded.
Explanation of [Switch-on diff.]
Optional: only with combination tank
With a combination tank, this parameter regulates how
far the current warm water temperature can fall before
the hot water tank again demands heat from the boiler.
If the value is set to 15 °C, the current hot water
temperature may drop by 15 °C from the value
[Hot water tank target]. The combination tank does not
demand heat from the boiler unless this happens.
With a combination tank, this value can be set to
approximately 5°C to 8°C if the amount of hot
water is insufficient.
Explanation [Circulation runtime]
Optional: only for circulation pump
This parameter specifies the duration for operating the
circulation pump after it has been started by the control
system. Once this time has expired, the circulation
pump is switched off for the set duration [Circulation
pause].
Example:
[Circulation runtime] = 3 minutes
[Circulation pause] = 10 minutes
If the circulation pump has been started, it is in
operation for 3 minutes and then disabled for
10 minutes. This means that it can only be requested
again by the control system after 13 minutes.
You can determine the required running time of
the circulation pump in the following way. Start
the circulation pump in the control system by means of
manual operation in the inputs and outputs menu. After
starting, measure the time until the fresh water module
warms up the return line for the circulation. This time
(e.g. 3 minutes) is required to heat the hot water pipe.
Then enter this time in parameter [Circulation runtime].
During this time measurement, no hot water may be
tapped (e.g. by sink, shower ...), because otherwise an
incorrect time is measured.
Explanation [Circulation pause]
Optional: only for circulation pump
This parameter sets the pause after a circulation pump
operation. The control system can only restart the
circulation pump after this pause/break has expired.
Example:
[Circulation runtime] = 3 minutes
[Circulation pause] = 10 minutes
If the circulation pump has been started, it is in
operation for 3 minutes and then disabled for
10 minutes. This means that it can only be requested
again by the control system after 13 minutes.
Explanation of [Enable circulation]
Optional: only for circulation pump
This parameter defines the minimum temperature of
the hot water tank for starting the circulation pump. The
circulation pump only starts once the hot water tank
has exceeded this temperature.
Содержание 13180LP-T
Страница 1: ...2018 05 24 EN 0000000313 V 005 3 43 0 3308 93222 001 Pellet boiler 180 220 kW Operation ...
Страница 29: ...ETAtouch controller Getting to know the control system 29 ...
Страница 39: ...ETAtouch controller BufferFlex function block 39 ...
Страница 47: ...ETAtouch controller Buffer function block 47 ...
Страница 51: ...ETAtouch controller Hot water tank function block 51 ...
Страница 55: ...ETAtouch controller Fresh water module function block 55 ...
Страница 69: ...ETAtouch controller Solar function block 69 ...
Страница 87: ......
Страница 88: ...www eta co at www eta co at downloads DOWNLOAD ...