- 10 - 

 

Cleaning  activities  create  risk  of  damaging  the  modules  and  array 
components, as well as increasing the potential electric shock hazard.   

 

Do not clean the modules during the hottest time of the day to avoid thermal 
stress on the modules.   

 

Cracked or broken modules represent an electric shock hazard due to leakage 
currents,  and  the  risk  of  shock  is  increased  when  modules  are  wet.  Before 
cleaning,  thoroughly  inspect  modules  for  cracks,  damage,  and  loose 
connections.   

 

During the daylight, the voltage and current present in the array are sufficient 
to cause a fatal electric shock.   

 

Please  make  sure  that  the  array  has  been  disconnected  from  other  active 
components before starting the cleaning.   

 

Wear  suitable  protective  clothing  (clothes,  insulating  gloves,  etc.)  when 
cleaning the modules.   

 

Do not immerse the module, partially or totally, in water or any other cleaning 
solution.   

 

Do not use such as lubricants and organic solvents to clean the connectors.   

 

Do not clean modules under the weather conditions of wind more than 4 class 
(in Beaufort scale), heavy rain or heavy snow.   

 

When cleaning the modules, it is forbidden to step on the modules, forbidden 
the injection of water to the backside of the modules or cables. Please ensure 
that  the  connectors  are  clean  and  dry  to  prevent  electric  shock  and  fire 
hazards.   

 

Do not use steam cleaner.   
For detailed requirements regarding cleaning, please refer to Manual for PV 
ModuleOperation and Maintenance, available from   
https://www.etsolar.hk/res-documents/ 
 

CLEANING METHODS   
 
Method A: Compressed water

   

 

Requirement for water quality:   

 

PH: 5 ~7;   

 

Chloride and Salinity

0 - 3,000 mg/L   

 

Turbidity

0-30 NTU   

 

Conductivity

1500~3000 μs/cm   

 

Total dissolved solids (TDS)

≤1000 mg/L   

 

Water hardness (calcium and magnesium ions)

0-40 mg/L   

 

Non-alkaline  water  must  be  used;  demineralized  water  shall  be  used  when 
conditions are available   

 

The maximum water pressure recommended is 4 MPa (40 bar)   
 

Method B: Compressed Air   

 

ET  Solar  recommends  using  this  method  to  clean  the  soft  dirt  (like  dust)  on 

Содержание ET-M660BH GL Series

Страница 1: ...www etsolar hk INSTALLATION MANUAL ET Solar Series Module Installation Safety instructions Maintenance Version 2021Q4...

Страница 2: ...Selecting the proper mounting structure and hardware 4 4 2 Mounting methods 4 4 2 1 Mounting with bolts 4 4 2 2 Mounting with clamping hardware 5 4 2 3 Installation position and static loads 6 5 Elec...

Страница 3: ...ompliance with this installation instruction may result in property damage and or physical injury ET Solar will not be liable for compensation of any loss or injury caused by this type of non complian...

Страница 4: ...re may go outside the above range please consult with ET Solar before installation The irradiance reflected on the rear of the bifacial solar modules shall not exceed 300W m2 Do not attempt to disasse...

Страница 5: ...y a factor of 1 25 when determining component voltage ratings conductor ampacity fuse sizes and size of controls connected to the module or system output An additional multiplying factor of 125 percen...

Страница 6: ...r to standard solar photovoltaic installation guides or a reputable solar installer or systems integrator Shading on the module will reduce electricity production Do not install the module near equipm...

Страница 7: ...big enough to fix the modules steadily Please find detailed mounting information in the below figure A 1 2 4 2 2 Mounting with clamping hardware When choosing clamp mounting method please be sure to u...

Страница 8: ...ion and static loads Maximum design load of the PV module by front 3600pa and back1600pa the safety factor of 1 5 times these values can vary depending on installation method of the modules please ref...

Страница 9: ...ET Solar recommends the negative pole of PV module array is connected to earth during all PV system installations That will keep optimal performance of PV Power Plants which are located in a hot high...

Страница 10: ...if hot spot occurred the diode will come into operation to stop the main current from flowing through the hot spot cells in order to prevent module over heated and performance loss Notice bypass diod...

Страница 11: ...keep PV modules clean The dirt such as bird droppings leaves dust is usually need to be cleaned When cleaning the modules make sure that the temperature difference between the water and the module is...

Страница 12: ...as lubricants and organic solvents to clean the connectors Do not clean modules under the weather conditions of wind more than 4 class in Beaufort scale heavy rain or heavy snow When cleaning the modu...

Страница 13: ...uation are not covered by ET Solar s warranty TROUBLE SHOOTING If your PV system does not work normally after installation please inform your installer immediately It is recommended to perform prevent...

Страница 14: ...ssumed by ET Solar for any infringement of patents or other rights of third parties which may result from use of the PV product No license is granted by implication or otherwise under any patent or pa...

Страница 15: ...www etsolar hk 13 Appendix 1 Electrical ratings of ET Solar modules Sheet 1 solar cell type 166mm...

Страница 16: ...www etsolar hk 14 Sheet 2 solar cell type 158 75mm...

Страница 17: ...www etsolar hk 15 Sheet 3 solar cell type 156 75mm mono si poly si Sheet 4 solar cell type 182mm...

Страница 18: ...www etsolar hk 16...

Страница 19: ...ABOUT MANUFACTURER ET SOLAR POWER HONGKONG LIMITED Room 01 21 F XINGFA Commercial Building 9th Tobacco Factory Street Mong Kok HongKong Tel 86 510 85382358 Fax 86 510 85382358 mail support etsolar HK...

Отзывы: