3 • INSTALLATION / ASSEMBLY / CONNECTION
Before installing the device, observe the following:
• Before installing the product, switch off the power supply.
• Information concerning the motion detector's range is based on an
installation height of 3 m.
• The greater the installation height, the wider the range, but the lower
the sensitivity.
• Movement diagonal to the detector is optimal for triggering the
detector (a direct and headon approach is more difficult and
therefore the range is significantly reduced.)
• The detector should be positioned according to spatial conditions
and requirements.
• Make sure that the detector has a clear line of sight, as infrared
beams cannot penetrate solid objects.
The presence detector features two separate
DIMMER light channels
.
Both
light channels
are synchronised
(C1 = C2)
in the factory settings.
Light channel C2
can be switched on after
light channel C1
.
Remember to bear this in mind when assigning lighting groups to the
channels. We recommend that you assign the “room interior” lighting
group to light channel C1 and the “window side” lighting group to
channel C2. Nevertheless, it is still possible to mount the presence
detector on the ceiling in any orientation (Fig. 2).
ESYLUX PD-C360i/24 DUODIMplus presence detectors are
composed of a power and a sensor section. Install the power section in
the required position
(Fig. 3)
and connect the presence detector as per
the circuit diagram
(Fig. 4)
.
➊
Standard operation
➋
Standard operation with additional control by means of a button
➌
Master/slave connection for presence detectors: a maximum of 10 slave
devices can be connected to the master device
As an option, settings can be performed using the DIP switch on the
back of the sensor (see DIP switch section). This must be done before
the device is activated. Plug the sensor section into the power section
and gently screw in place.
4 • START-UP
Connect the power supply
• A warm-up phase of approx. 25 seconds is initiated.
The
red (light channel 1 = C1)
,
green (light channel 2 = C2)
and
blue LEDs
flash alternately. During the process, the connected lighting is
switched on.
The detectors are preset to
factory settings P1/remote control
and are
therefore immediately ready for use after the warmup phase.
Содержание PD-C360i/24 DUODIMplus-FM
Страница 3: ...ABB FIG 4 ABB FIG 5 ABB FIG 6 6 1 6 2 PD C360i 24 DUODIMplus FM PD C360i 24 DUODIMplus SM...
Страница 104: ...RU 104 3 3 DIM C1 C2 C2 C1 C1 C2 2 ESYLUX PD C360i 24 DUODIMplus 3 4 Master Slave Master 10 Slave DIP DIP 4 1 C1 2 C2 P1...
Страница 107: ...RU 107 S1 S3 C1 C2 S1 100 C3 S1 S3 C3 1 2 C3 S3 S1 S3 ECO C1 C2 S1 S1 C3 S1 S3 C1 C2 S1 100 C3...
Страница 108: ...RU 108 C1 C2 C3 S3 10 40 8 MOBIL PDi plus 6 8 S1 S3 C1 C3 DIM S1 S3 C1 C3 OK DIM S1 S3 C1 C3 S1 S3 C1 C3 1 3 2 Blue Mode...
Страница 109: ...RU 109 Taste C1 C2 100 10 C1 C2 C3 DIM 100 750 3 100 3 100 C1 C2 C3 10 40 10 10 40 10...
Страница 112: ...112...
Страница 113: ......