GB
17
Programming
The following functions can only be programmed when the device is
in programming mode. All changes are stored and the functions are
implemented after exiting programming mode.
Enter programming mode
Blue LED
lights up to indicate programming mode.
Light channel C1
is switched on with 100 % luminous
efficiency. The detector’s movement sensor is
disabled whilst the device is in programming mode.
Exit programming mode
Blue LED
goes out; the settings are now stored.
The detector will now operate automatically
according to the preset values.
NOTE: If programming mode is not exited by
pressing the button, the detector automatically
exits programming mode 10 minutes after the last
button was pressed. All functions set up until this
point will be stored.
End the "test"/manual light ON/OFF/time setting function
Return to preset mode
Channels 1 – 2 remain permanently switched on during test mode.
Each time a movement is detected, the
blue mode
LED
flashes twice, regardless of the ambient lighting
level. Press the
"Reset"
button to exit. If a slave signal
is detected, the
blue LED
will flash 4 times.
Selecting the channel to be programmed
Acknowledgement:
C1 =
red and blue LEDs
flash
C2 =
green and blue LEDs
flash
When the
"DIM"
button is pressed once, the dimmer
automatically starts to slowly adjust the light intensity of the
lighting from the maximum to the minimum value. When the
required ambient brightness level has been reached, press
the
"Eye"
button. The new brightness set value is then stored.
Setting the brightness set value (100 lux – 750 lux)
Acknowledgement:
red and blue LEDs
flash three times,
light is automatically adjusted to the set value.
Daytime operation setting (2,000 lux)
Acknowledgement:
red and blue LEDs
flash three times
(channel 1), no light measurement, light is only
activated by presence.
Time setting for C1 + C2 (HVAC)
If no movement is detected, the time setting starts.