MA
01
994
30
0
EN
Configuration
29 / 106
– If the measured brightness level falls permanently below the
brightness setpoint when presence is continuously detected (plus
follow-up time), the light is switched on and light output is con-
tinuously controlled.
– If the measured brightness level is permanently above the bright-
ness setpoint, the light is switched off.
–
Closed-loop light control
(the special case)
How it works: Lighting is switched with a preset, adjustable light
output.
Relevant parameter: Brightness switching value
Technical implementation: When open-loop light control is deacti-
vated, the light is controlled to a defined light output.
– If the measured brightness level falls permanently below the
brightness switching value when presence is continuously
detected (plus follow-up time), the light is switched on and con-
trolled to the defined light output.
– If the measured brightness level is permanently above the bright-
ness switching value, the light is switched off.
App
Changing from automatic light control to light control is done in the
<Light> menu. For details see
.
Adjustable parameters
Separate parameter settings apply for open-loop and closed-loop light
control. For details see
5.1.4
Minimum constellations
Depending on the operating mode of a group, the following devices/
instances must or can be present and configured in this group:
For details see
Operating mode
Presence detec-
tor
Light sensor
Push-but-
ton
Switch
Actuator
Control gear
(lighting)
Fully automatic
x
o
o
o
x
*
x
*
Semi-automatic
x
o
x
o
x
*
x
*
Manual operation
–
o
x
o
x
*
x
*
x
o
–
*
Absolutely necessary
Possible
Without effect
Control gear or switching actuator component required