Fault finding

Signal / fault description

all LED displays are dark (without mains 230 V / 50 Hz)

the green LED

is dark

the yellow LED

malfunction flashes: 0000000010, flashing

sequence 1 x brief

the yellow LED

malfunction flashes: 0000001010, flashing

sequence 2 x brief

the yellow LED

malfunction flashes: 0000101010, flashing

sequence 3 x brief

the yellow LED

malfunction flashes: 0010101010, flashing

sequence 4 x brief

the yellow LED

malfunction flashes: 1010101010, flashing

sequence 5 x brief

unvolontary SHE activation - (SHE man. call point or detector

had

been activated)

it is imposible to close the door of the TRZ Basic DG

not

Explanation / possible source of malfunction

discharge totally battery, take off fuse F3 (battery) disconnect

emergency batteries and wait at least 2 min. Replace by
emergency batteries and connect them, replace fuse F3.

mains connection out of order
mains fuse defective
battery out of order
battery fuse defective

mains failure
mains fuse defective
no input voltage present (230 V / 50 Hz)

no battery connected
battery incorrectly connected
discharge totally battery - replace it!
battery fuse defective - replace it!

cable break feed line SHE-switch
missing or incorrect end resistor (correct value 10kOhm

cable break feed line detector
defective detector
missing or incorrect end resistor (correct value 10kOhm)

cable break feed line of pressurized gas generators
fuse defective
slide switch are in position “secured”

incorrect line termination (ER) in the SHE man. call point

(correct value 10kOhm)

shortcircuit in the triggering circuit of the SHE-man. call point or

autom.detector

the connected cores touch the TRZ Basic DG door
batteries incorrectly placed

new

à

à

à

à

à

à

à

à

à

à

à

à

à

à

à

à

à

à

à

à

à

à

à

à

!

!

!

OK

!

!

If the source of fault could not be analysed by the means of this chart, please procede as follows:

switch the TRZ Basic DG completely voltage free (mains and battery)

disconnect all connected lines - except from the mains

create

line monitoring directly in the TRZ Basic DG control panel

install the end resistor “SHE-man. call point” in the terminals 12 and 17

install the end resistor “autom. detector” in the terminals 18 and 19

restablish power supply (mains and battery)

the control panel must

not signal any malfunction, green LED

is shining, yellow

and red LED

displays are dark.

(the fault has an external source)

restablish the external connections

(do not forget monitor diodes and end resistors), check after each connection, if the fault is eliminated!

check if the feed lines for

the SHE man call point, autom. detectors and electromagnetic clamps do not present any break or twisting

connections have to be

check

check individual components for visible faults.

(the fault has an internal source)

check the mains voltage

check the battery

check

the fuses

check the monitor diodes and the end resistors

check the slide switch.

à

à

à

à

à

à

à

à

à

à

à

à

à

à

à

the TRZ Basic DG does not signal any malfunction

one after the

other

all

the TRZ Basic DG does signal a malfunction

OK

!

D
GB

Содержание TRZ Basic DG

Страница 1: ...rms to current state of the arts standards processor controlled versatile connection facilities hours of functioning guaranteed in case of power failure Zum Anschluss von 24 V DC Druckgasgeneratoren To connect 24 V DC pressurized gas generators Diese Bedienungsanleitung für späteren Gebrauch bzw Wartung aufbewahren Please keep these operating instruction for future reference and maintance Änderung...

Страница 2: ...nstallation Read and observe the information contained in these operating instructions and respect the order of procedure stated therein Please keep these operating instructions for future reference and maintenance Reliable operation and the prevention of damage and risks are only granted if the equipment is assembled carefully and the settings are carried out according to these instructions and t...

Страница 3: ...be disconnected at all poles before maintenance work or structural alterations and After installation Attention Manufacturer s declaration Safety instructions Sicherheitshinweise Manual activation in case of fire smoke alarm Note Automatic activation in case of fire smoke alarm Note Smoke heat extraction pressurized gas generators activate Smoke heat extraction dome lights closing no Smoke heat ex...

Страница 4: ...n gut sichtbar und erreichbar sein Nicht hinter Wandvorsprünge Türflügel oder verdeckt montieren Steuerzentrale öffnen und an den vorgegebenen 4 Bohrungen am Baukörper befestigen Für geeignetes Befestigungsmaterial ist zu sorgen Bedienelemente Antriebe Anschlussdosen max 1 2 m zum Antrieb und automatische Melder nach deren beiliegenden Bedienungsanleitungen montieren Entsprechende Vorschriften sie...

Страница 5: ...ystem RWA Bedienstelle max 10 Stück SHE manual call point max 10 pieces autom Melder autom detector autom Melder autom detector Rauchabzugsklappe Lichtkuppel NRWG Smoke vent domelight Auslöseeinrichtung Druckgasgenerator mit CO Flasche 2 Releasing device with CO bottle 2 pressurized gas generator pneumatischer Hubzylinder pneumatic lift cylinder Rauchabzug Smoke heat extraction Rauchabzug Smoke he...

Страница 6: ...ned for maximum wiring cross sections of 2 5 mm If larger cross sections are used then the cross section must be reduced in size immediately ahead of the central control unit In all circumstances the types of wiring are to be agreed with the site management with the local authorisation authorities energy supply companies fire protection department or health and safety organisation In cases where t...

Страница 7: ...tkuppel NRWG Smoke vent dome light Rohrleitung Stahl 6 x 0 7 mm von Auslöse einrichtung zum NRWG Pneumatikzylinder Pipeline made of steel 6 x 0 7 mm from SEC release station to the pneumatic cylinder Netz 230 V AC Mains supply 230 V AC Auslöseeinrichtung Druckgasgenerator mit CO Flasche 2 Release station pressurized gas generators with CO bottle 2 Rauchabzug Smoke heat extraction autom Melder auto...

Страница 8: ...3 5 8 4 2 6 EW 1 EW OK 12 13 14 15 16 17 18 19 Endwiderstand 10 k Ohm EW in der Zentrale aufklemmen falls keine RWA Bedienstelle und oder autom Melder angeschlossen ist Install end resistance 10 k Ohm EW in the control panel if no SHE manual call point and or smoke detector is connected 18 19 ein autom Melder one autom detector 1 5 2 4 AM 1 2 3 4 5 6 Endwiderstand 10 k Ohm End resistance 10 k Ohm ...

Страница 9: ...MAS are included in the delivery of the TRZ Basic DG TRZ WRMAS Basic The following components can be connected 1 x pot free transmission Alarm SHE activation 1 x pot free transmission collect malfunction charge on contact max 24 V max 0 5 A D GB 9 Zusatzmodule Additional modules 4 5 6 7 20 212223 TRZ WRMAS Erweiterungsleiste extension ledge Schließerkontakt Alarm RWA closing contact alarm SHE Öffn...

Страница 10: ...t stecken 2 2 2 2 2 2 2 2 2 2 2 2 Without mains voltage and without battery With mains voltage and battery Visual display in the control centre SHE manual call points Test emergency power supply Test automatic detectors Check all parts mechanically and electrically for fully tightened screw connections and damage the terminals plug in connectors for pressurized gas generators and control elements ...

Страница 11: ...szeit 4 Jahre aus zutauschen Bei der Entsorgung der verwendeten Gefahrstoffe z B Akku s Gesetze beachten à à à à à à à à à Display operating OK is not shining The electromagnetic clamps open without pressing a switch Malfunction beep code chart The operating instructions of the connected components must imperatively be observed in the SHE manual call points and the control panel a malfunction has ...

Страница 12: ...kt 0000101010 Blinkfolge 3 x kurz gelbe LED Störung blinkt 0010101010 Blinkfolge 4 x kurz gelbe LED Störung blinkt 1010101010 Blinkfolge 5 x kurz ungewollte RWA Auslösung RWA Taster oder Melder wurde ausgelöst die Tür der TRZ Basic DG läßt sich nicht schließen nicht Erklärung Mögliche Fehlerursache à à à à à à à à à à à à à à à à à à à à à à à à Akku tiefentladen Sicherung F3 Akku entfernen Notstr...

Страница 13: ...e switch are in position secured incorrect line termination ER in the SHE man call point correct value 10kOhm shortcircuit in the triggering circuit of the SHE man call point or autom detector the connected cores touch the TRZ Basic DG door batteries incorrectly placed new à à à à à à à à à à à à à à à à à à à à à à à à OK If the source of fault could not be analysed by the means of this chart ple...

Страница 14: ...wenkbarer Deckel abschließbar H x B x T FKS 2A FKS 5A Operating voltage power connection 230 V AC 50 Hz 10 separately fused Current consumption mains max 0 6 A Power consumption approx 75 VA System voltage 24 V DC nominal 15 25 Residual ripple 1 Emergency batteries 2 x 12 V 1 2 Ah with total discharge prot in case of low voltage monitor funct for wire breakage and fuse failure charging time approx...

Страница 15: ...g F2 Druckgasgeneratorsicherung F3 Akkusicherung Key mains fuse pressurized gas generator fuse battery fuse PE DG DG 10k OK 3 1 10k 10k A 1 DG DG 1 2 3 L N PE gesichert secured Netzleiter phase conductor Netz 230 V AC mains 230 V AC Neutralleiter neutral conductor Schutzleiter PE conductor scharf active RAUCHABZUG SMOKE VENT AUF OPEN 10k in letzten RWA Taster 10k in last SHE man call point Masse G...

Отзывы: