MAGPRO16 Addressable Fire Alarm Panel – Installation and Programming Manual
20
5. PROGRAMMING OF MAGPRO16 FIRE ALARM PANEL
5.1. General Information for Programming and Operation
Addressable fire alarm panel MAGPRO16 can be programmed directly through the navigation and functional digit
buttons on the front panel. The programming menus are organized in a text tree-structure and are viewed on the LCD-
display (4 rows x 40 symbols). The access to the programming menus is organized in three levels
– see items 5.2.
When turned on, the panel always runs a procedure of loading the parameters, which usually takes about 5-6 sec.
There is no access to the menus of the panel during that procedure.
Upon the initial startup, the panel does not hold any configurations. Initialization may take several minutes. The
initialization time needed depends on the number of periphery and loop devices
– for Loop 1 and Loop 2. After the
panel has been turned on, it performs a procedure for detecting newly installed loop devices
– see also APPENDIX C,
page 48.
During the procedure the symbol “ ” is blinking in the up right corner of the screen. This symbol will appear always
when running similar procedures like resetting of devices or recognized new devices connected to the loop.
Right after the initial startup of the mains power supply and initialization completed the panel turns to normal operation
mode. If there are any active alarm and fault messages they are displayed on the screen, as the indication follows the
priority:
Indication - Groups
Priority
ALARMS
The highest
FAULTS
High
DISABLEMENTS
Normal
TESTS
Normal
WARNINGS
Low
The name of the current active indication group is blinking together with the number of the first message. Press the
ENTER button to review some additional information for the respective message as data and time of occurring, device
address, zone number or other, according the trouble type.
The indication for the active ALARMS in the system is viewed with highest priority.
The addressable fire alarm panel MAGPRO16 supports different languages for the programming menus.
The factory default setting of the language is in English. You can change the language after the initial power-
up as enter in sequence:
Press CANCEL
– enter code 3333 – select menu 6) GENERAL SETTINGS – menu 6.4) PANEL SETTINGS –
Button 1
– Button ENTER
Use the ENTER button to enter in programming menus and confirmation of entered values and
parameters; the functional digit buttons are used for entering of access codes and changing the
current status; the navigation buttons (up/ down and left/ right arrows) are used for scrolling
through the menus and for changing the editing field.
5.2. Codes and Access Levels
There are three access levels in MAGPRO16 panel: User, Maintenance and Installer. Every level comprises different
functions and operations. To enter Maintenance and Installer levels is necessary to enter valid access code:
Level Description
Code
Combination
Access
1
User
-
Only
Silence buzzer
and
Evacuation*
buttons are active. It is not allowed to
enter Maintenance and Programming access levels.
* Just for that cases, when the fire alarm signal is received from a device
2
Maintenance
2222
Silence buzzer, Silence sounders, Reset
and
Evacuation
buttons are active.
Maintenance access level entry, which allows partial programming and menu
settings.
3
Installer
3333
Silence buzzer, Silence sounders, Reset
and
Evacuation
buttons are active.
Installer access level entry, which allows full programming and settings.
The introduced
code combinations are visualized with “ “ symbol. The entry is automatic.