Oxygen detectors – URS20SE 

16/06/2017 

Gas detection systems for industrial environments 

7/8

 

 

Checklist after 
mechanical and 
electrical installation 

(continued)

 

output must be set between 14 and 16mA (theoretic value 15.1mA). 

Use  the  calibration  kit  to  apply  the  gas  mixture  at  4%  of  CO

2

,  making  sure  the 

4...20mA output is between 5 and 7mA (theoretic value 6.1mA); the status LED and 
the pre-alarm, 1

st

 and 2

nd

 alarm threshold relays on the optional relay card switch on 

according to the thresholds and the alarm mode settings. 
 

Maintenance

 

Routine 
 

Corrective 

 
 
 
 
 
 
 

Decommissioning

 

A sensor functional test should be carried out every three-six months. 

Routine  maintenance  involves  repeating  the  same  tests  as  set  forth  in  “checklist 
after 

mechanical and electrical installation”.

 

If any abnormalities are found during routine sensor maintenance, return the sensor 
concerned  to  the  supplier  /  installer,  who  in  turn  will  send  it  back  to  the 
manufacturer. 
Sensors  may  need  to  be  re-calibrated,  using  the 

TUL40..

  calibration  kit  and  the 

TUS40-20

  handheld  terminal,  which  must  be  connected  to  the  sensor  via  the 

communication interface integrated in the cable (on the connector 

CN4

). 

 

For  the  re-calibration  procedure,  see  the  instructions  supplied  with  the  handheld 
terminal. 

Remove power from the detector, disconnect all  wiring and conduits and dismount 
the housing from all the blocking systems. 
 

Warranty 

Warranty  on  EsiWelma  products  is  valid  for  12  months  from  installation  date  and 
no  longer  than  24  months  from  manufacturing  date  on  the  product.  Installation 
data,  stamp  and  signature  on  the  data  sheet  filled  in  by  the  installer  will  be 
considered proof for warranty. 

 

A copy of the warranty data sheet must be sent when returning the product under 
warranty. 

 

Accessories 

UZR20.4

 Four-relay card 

TUL40..

 Gas calibration Kit 

TUS40

 Handheld terminal 

CRG40

 Gas collecting cone 

PAP40

 Powerful jets protection 

 

Dimensions and weight 

 

Dimensions (HxWxD): 164x100x82mm.                                                Weight: 0.8Kg 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Содержание Sensigas URS20SE

Страница 1: ...entres and more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deplete the oxygen in the air URS20SE sensors...

Страница 2: ...default Consumption mode applications at 1 or 2 thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1st threshold alarm 20mA 2nd threshold alarm by jumper selectable pol...

Страница 3: ...n this case the detectors must be located at the breathing height of the occupants in the premises Take into consideration the following specific installation guidelines as well as the above instructi...

Страница 4: ...iameter of the cable gland Default settings of the sensor are shown in the Technical Specifications chapter In order to change the default settings switch off the power supply input the new settings a...

Страница 5: ...ions below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connect...

Страница 6: ...factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended The detector will enter a 2 minute w...

Страница 7: ...rned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 handheld terminal which must be c...

Страница 8: ...industry 2 Equipment category 2 for use in Zone 1 G Equipment intended for use in explosive gas atmosphere caused by mixture of air and gas vapours flammable mist Ex d IIC T6 Type of protection compl...

Отзывы: