Oxygen detectors – URS20SE 

16/06/2017 

Gas detection systems for industrial environments 

2/8

 

 

Technical 
characteristics 

 

Type of sensor 

Electrochemical cell 

Detectable Gas 

O

excess 

O

2

 deficiency 

Power supply 

11÷28Vdc 

Max power consumption 

2.5W 

Measuring range  

0…30% O

2

 

Precision 

 2,5% of full scale range (in air) 

Repeatability 

 2,5% of full scale range 

Measurement resolution 

0.1% O

2

 

Microprocessor resolution 

1024 points (10 bit) 

Digital filter system 

Kalman Filter 

Watchdog 

Internal 

Warm-up time 

< 2m 

Stabilization time 

< 2m 

Response time 

< 10s (T20), < 45s (T90) 

Average Sensor life (in air) 

120 weeks 

Sensor type settings 
(O

2

 excess or deficiency) 

S1.7 DIP switch 

OFF (O

2

 excess) 

S1.7 DIP switch 

ON (O

2

 deficiency) 

Threshold limit settings  
(S1.8 = OFF, default): 

Pre-alarm 

1

st

 threshold alarm 

2

nd

 threshold alarm 

 
 

23% O

2

 

25% O

2

 

27% O

2

 

 
 

19% O

2

 

17% O

2

 

15% O

2

 

Threshold limit settings  
(S1.8 = ON): 

Pre-alarm 

1

st

 threshold alarm 

2

nd

 threshold alarm 

 
 

22% O

2

 

23% O

2

 

24% O

2

 

 
 

20% O

2

 

19% O

2

 

18% O

2

 

4..20mA Output 

Proportional mode 
(default) 

 

Consumption mode 
(applications at 1 or 2 
thresholds) 
4…20mA Output reference 
selection: 

 
-   4mA   =   0% O

2

 

- 20mA   = 30% O

2

 

 
-   0mA   = no alarm 
- 10mA   = 1

st

  threshold alarm 

- 20mA   = 2

nd

  threshold alarm 

 
by jumper selectable polarity 

4…20mA output load resistor 

- up to 200

 at 12Vdc power supply 

- 200

 

 700

 at 24Vdc power supply 

Operating Temperature 
Storage Temperature

 

-20 

 50 °C 

-20 

 70 °C

 

Relative Humidity 

(without condensing) 

-

 

Operation 

-

 

Storage

 

 

15 

 90 %RH 

45 

 75 %RH

 

Operating pressure (KPa) 

80 

 110 

Air speed (m/s) 

 6 

Visual warnings 

Red LED visible with detector energized 

Dimensions and weight 

See dedicated section 

Options & Accessories 

 

Card with 4 SPDT relays 

UZR20.4

 

NO or NC contacts available, jumper 
selectable 

See threshold limit settings 

Maximum relay capacity: 

50mA at 24Vac/dc, 100mA at 12Vac/dc 

Relay operating mode: 

-

 

direct: relay ON when an event is 
detected 

-

 

reverse: relay ON when no event is 
detected 

TUL40..

 Gas calibration kit 

See installation and commissioning chapter 

TUS40   

Handheld terminal   

for service and maintenance  

See installation and commissioning chapter 

CRG40

   Gas collecting cone 

See dedicated data sheet 

PAP40

   Powerful jets protection 

See dedicated data sheet 

 

ATEX markings 

1370   

 II 2G   Ex d IIC T6 

 
BVI 07 ATEX 0032 
-20°C 

 T

A

 

 +50°C 

Содержание Sensigas URS20SE

Страница 1: ...entres and more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deplete the oxygen in the air URS20SE sensors...

Страница 2: ...default Consumption mode applications at 1 or 2 thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1st threshold alarm 20mA 2nd threshold alarm by jumper selectable pol...

Страница 3: ...n this case the detectors must be located at the breathing height of the occupants in the premises Take into consideration the following specific installation guidelines as well as the above instructi...

Страница 4: ...iameter of the cable gland Default settings of the sensor are shown in the Technical Specifications chapter In order to change the default settings switch off the power supply input the new settings a...

Страница 5: ...ions below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connect...

Страница 6: ...factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended The detector will enter a 2 minute w...

Страница 7: ...rned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 handheld terminal which must be c...

Страница 8: ...industry 2 Equipment category 2 for use in Zone 1 G Equipment intended for use in explosive gas atmosphere caused by mixture of air and gas vapours flammable mist Ex d IIC T6 Type of protection compl...

Отзывы: