Throubleshooting 

Effect 

Possible cause 

NC valves type do not open 

  Valve not connected 

  No power 

  NO valve type instead of NC type 

  Incompatible valve type 

(power absorption > 26W total) 

  Alarm not reset or current 

  Current sensor preheating phase 

  All sensors defective 

  General Fault presence 

(NO) valve type 
does not close 

  Valve not connected 

  Sensor not in alarm condition 

  Cable interrupted 

RESET button does not 
restore default conditions 

  A sensor still in alarm condition 

  Control unit fault 

(Control unit Yellow LED OFF) 

OUTPUT Test button does 
not work 

  Current fault / alarm 

 

Connections 

E

V

G

G0

C1 S1 A1

+

-

C

NC

NO

C

NC

NO

+

-

Batt

C2 S2 A2

C3 S3 A3

C4 S4 A4

E

V

ALARM

FAIL

 

 

24 V AC power supply, voltage  

G0 

 

24 V AC power supply, system neutral  

C1 

 

Sensor input 1 (common) 

S1 

 

Sensor input 1 (signal) 

A1 

 

Sensor input 1 (power) 

C2 

 

Sensor input 2 (common) 

S2 

 

Sensor input 2 (signal) 

A2 

 

Sensor input 2 (power) 

C3 

 

Sensor input 3 (common) 

S3 

 

Sensor input 3 (signal) 

A3 

 

Sensor input 3 (power) 

C4 

 

Sensor input 4 (common) 

S4 

 

Sensor input 4 (signal) 

A4 

 

Sensor input 4 (power) 

 

Valve output 12VDC 

 

Valve output 12VDC 

alarm 

Alarm relay output (common) 

NC 

alarm 

Alarm relay output (normally closed contact) 

NO 

alarm 

Alarm relay output (normally open contact) 

fail 

Fault relay output (common) 

NC 

fail 

Fault relay output (normally closed contact) 

NO 

fail 

Fault relay output (normally open contact) 

Batt 

Battery output  + 

Batt 

Battery output  - 

 

Hooter output  + 

 

Hooter output  - 

 

 

  

Layout 

 

s

LYC18

LED
TEST

RESET

OUTPUT
TEST

1

2

3

4

G    G0

24V

C1

  

S1

  

A1

E     V

C   NC  NO

C2

  

S2

  

A2

C3

  

S3

  

A3

C4

  

S4

  

A4

VALVE / TYPE

VALVE / MODE

NC

NO

CONT.

PULSE

+    -

Batt.

F1

3A

FAIL

C   NC  NO

ALARM

E     V

+    -

1

2

7

8

9
10

14

15

11

12

13

3

4

5

6

 

1  Battery connection terminal 

9  Alarm and Fail relay outputs 

2  Battery protection fuse T3.15A 

10 12VDC 300mA max hooter output 

3  12V valve terminals 

11 LED Test button 

4  Control Unit status LEDs 

12 OUTPUT Test button 

5  Sensors status LEDs 

13 RESET button 

6  Valve Mode Jumper 

14 Remote sensors terminals 

7  Valve Type Jumper 

15 Not used 

8  24VAC power supply terminal 

   

   

   

 

Due to our policy of continuous product improvement, 
specifications are subject to change without notice.

 

Wiring diagrams 

Control unit UCE18 with 4 sensors and n.2 12VDC solenoid valves. 12V buffer 
battery and external hooter. Optional devices (lamps, extractors). 

Y1  

 24V AC

G

G0

G

G0

E

V

B1

C   S   A

C

1

  

S

1

  

A

1

+

-

N O   N C

 C 

M1

V1

 230V AC

L

N

BATT.

N1

C   S   A

C   S   A

C   S   A

B2

B3

B4

Y2  

L1

N O   N C

 C 

alarm

fail

C

2

  

S

2

  

A

2

C

3

  

S

3

  

A

3

C

4

  

S

4

  

A

4

+

-

 H1

M

E

V

M

R

18Kohm 1/4W termination resistor   

to be used in place of  sensor

 

N1 

Control unit UCE18 

B1 ÷ B4 

Sensors UR.13/A 

Y1 ÷ Y2 

Solenoid valves 12VDC 

H1 

External hooter 12VDC 300mA max 

V1 

Battery 12V 6÷10Ah (not supplied) 

M1 - L1 

Auxiliary devices (lamps, extractors, etc.). 

Control unit UCE18 with con 4 sensors and

 

230VAC solenoid valve. External 

hooter 12V. Control of optional auxiliary devices (signal lamps etc). 

Y1

 24V AC

G

G0

G

G0

E

V

B1

C   S   A

C

1

  

S

1

  

A

1

+

-

N O   N C

 C 

 230V AC

L

N

BATT.

N1

C   S   A

C   S   A

C   S   A

B2

B3

B4

L1

N O   N C

 C 

alarm

fail

C

2

  

S

2

  

A

2

C

3

  

S

3

  

A

3

C

4

  

S

4

  

A

4

+

-

 H1

M

E

V

Rv

R

18Kohm 1/4W termination resistor  
to be used in place of sensor

1.8Kohm 1/2W termination 
resistor to be used in place  
of solenoid valve

 

N1 

Control unit UCE18 

Rv 

Factory supplied 

B1 ÷ B4 

Sensors UR.13/A 

Y1 

Solenoid valve 230VAC  

H1 

External hooter 12VDC 300mA max 

L1 

Auxiliary devices (signal lamps, etc.). 

 

Dimensions 

UCE18

 

155

10

6

8

9

174

56.5
47.9

31

s

LYC18

LED
TEST

RESET

OUTPUT
TEST

1

2

3

4

G    G0

24V

C1

  

S1

  

A1

E     V

C   NC  NO

C2

  

S2

  

A2

C3

  

S3

  

A3

C4

  

S4

  

A4

VALVE / TYPE

VALVE / MODE

NC

NO

CONT.

PULSE

+    -

Batt.

F1

3A

FAIL

C   NC  NO

ALARM

E     V

+    -

 

UR.13/A 

                     

 

Dimensions in mm 

 

 

 

UCE18 

UCE18 

Отзывы: