Technical Data 

Control Unit UCE18 

 

Power supply voltage 

24VAC +/- 10% 

Frequency 

50/60Hz 

Power consumption 

32VA max (with battery under charge) 

Sensor inputs 

4 x UR.13/A 

Control outputs 

- 2 Electronic 12VDC (26W max total) 

 

- 2 SPDT Relays 250V 5(3)A 

Controlled valve type 

Normally Closed or 
Normally Open 

Operation logic 

positive (normally energized relays,  

 

de-energize in case of alarm / fault) 

 “

VALVE TYPE

” Jumper 

 

       Valve type  

NO = Normally Open (type 

 

NC = Normally Closed 

VALVE MODE

” Jumper 

 

       Valve output mode 

C

ONT 

=

 

continuous 

        (for NO type only) 

P

ULSE 

=

 

pulses (1 pulse every 10s) 

Optical signals 

(please refer to functional tables) 

 

Green LED 

Power presence / test 

 

Control U. Yellow LED  Valve(s) / control unit fault 

 

Sensors Yellow LEDs  Sensor fault  

 

Red LEDs 

Gas alarm 

Sensors connection length  cable 1.5mm

2

 max 80m 

Valve(s) connection length  cable 1.5mm

2

 max 80m 

(one cable per valve) 

cable 1.5mm

2

 max 40m (2 x 13W) 

Battery protection fuse 

T3.15A 250V 5x20 

Dimensions 

174 x 106 x 56.5 mm 

Protection  

IP20 – EN60529 

Room temperature 

0…50°C 

Room humidity 

Max 90% R.H. non condensing 

Sensors UR.13/A

 

 

Sensing element 

Tin dioxide semiconductor 

Intervention threshold 

 

 

URG13/A 

20% LEL methane (10000ppm) 

 

URG13.P/A 

20% LEL LPG (3720ppm) 

 

URO13/A 

200 ppm CO 

Protection 

IP44 (if correctly installed) 

Average life time  

5 years from installation date 

Room temperature 

0…50°C 

Room humidity 

Max 90% R.H. non condensing 

Built-in relay 

 

Operation 

Positive logic (normally energized).  

 

de-energizes in case of alarm / fault 

Changeover contact 

Voltage free 250V 5(3)A 

Built-in battery charger 

 

Charge voltage 

13.8VDC 

Charge current 

0.5A max 

Battery 

12V   6÷10 Ah (not supplied) 

 

Automatic intervention and current limit 

 Conformity 

 

 

Regulations 

Low Voltage 

2014/35/UE 

 

Electromagnetic Compatibility 

2014/30/UE 

Standards 

EN50194 

 

EN50270 
 

CAUTION 
Lifetime of sensors URG13/A, URG13.P/A e URO13/A is 5 
years from installation date. It is necessary to substitute 
them systematically before the end of the 5th year of use.

 

Average lifetime of sensors has been calculated considering a typical 
usage  in  an  environment  free  of  pollution  substances  (gases, 
solvents,  etc.).  A  frequent  presence  or  high  concentration  of  these 
substances  may  accelerate  normal  oxidation  process  of  the  sensing 
element and consequently shorten its decay time (lifetime). 

Functional tables 

                  

LEDs status 

 

 

Functions

 

 

 

Green 

LED 

 

 

Control U. 

yellow LED 

 

 

Sensor 

yellow LED 

 

 

Sensor 

red LEDs 

Sensors preheating (1min) 

Flash 1Hz 

ON 

ON 

ON 

TEST phase (3 min) 

Flash 2Hz 

ON 

ON 

ON 

Normal operation 

ON 

ON 

ON 

ON 

Gas alarm  

ON 

ON 

ON 

Flash 1Hz*  

Valve fault 

ON 

Flash 1Hz  

ON 

ON 

Sensor fault (up to 3) 

ON 

ON 

Flash 1Hz* 

OFF* 

Sensor fault (all) 

ON 

OFF 

Flash 1Hz 

OFF 

Ext. hooter alarm 

ON 

Flash 2Hz 

ON 

ON 

General fault 

ON 

OFF 

OFF 

OFF 

* for relative sensor(s) in alarm/fault

 

         

Output status 

 

 

 

Functions

 

 
 
 
 

2 EV outputs 

(NC valve) 

 

 

 

Alarm  relay 

output 

 

 

 

Fail relay      

output 

 

 

 

Hooter 

output 

Sensors preheat.(1 min) 

Voltage 

absence 

De-energized 

De-energized 

Inactive 

TEST phase (3 min) 

Voltage 

presence 

Energized 

Energized 

Inactive 

Normal operation 

Voltage 

presence 

Energized 

Energized 

Inactive 

Gas alarm 

Voltage 

absence 

De-energized 

Energized 

Active 

Valve fault 

Voltage 

absence 

Energized 

De-energized 

Active 

Sensor fault (up to 3) 

Voltage 

presence 

Energized 

De-energized 

Active 

Sensor fault (all) 

Voltage 

absence 

De-energized 

De-energized 

Active 

Ext hooter fault 

Voltage 

presence 

Energized 

De-energized 

Active 

General fault 

Voltage 

absence 

De-energized 

De-energized 

Active 

Simultaneousness of  2  or more  events  causes  a  combined  manage-
ment of LEDs and outputs in accordance with a defined priority. 
 

IMPORTANT

 

IN  CASE  OF  ALARM  FOR  GAS  LEAK  OR  CARBON 
MONOXYDE PRESENCE ACT AS FOLLOWS: 

 

Cut off all free flames and all gas-supplied devices 

 

Do not switch-on or switch-off electrical lights or any other 

electrically-supplied  appliance,  in  order  to  avoid  the 

sparkling (cause of explosion for explosive gas) 

 

Close the main valve of gas network or of LPG gas bottle 

 

Open windows and doors to ventilate the rooms 

 

Look for the cause of alarm, and eliminate it. If you are not 

able  to  find  and  to  eliminate the  cause  of the  alarm,  leave 

the building, and, from the outside, call for emergency aids. 

 

Environmental compatibility and disposal

 

This  product  was  developed  and  manufactured  using  materials  and 
processes which take full account of environmental issues and which 
comply with our environmental standards. 
Please note the following for disposal at the end of the product life, or 
in the event of its replacement:

 

 

For  disposal,  this  product  is  defined  as  waste  from  electrical 
and electronic equipment (“electronic waste”); do not dispose of 
it  as  household  waste.  This  applies  particularly  to  the  PCB 
assembly. 

 

Observe all current local laws and regulations.

 

 

Always  aim  for  maximum  re-use  of  the  basic  materials  at 
minimum environmental stress. Observe any notes on materials 
and disposal that may be attached to individual components.

 

 

Use  local  depots  and  waste  management  companies,  or  refer 
to  your  supplier  or  manufacturer  to  return  used  products  or  to 
obtain  further  information  on  environmental  compatibility  and 
waste disposal.

 

 

The  UCE18  shipping  case  can be recycled. Retain it for future 
use or in case of product return to the manufacturer

 

C  NC NO

C  NC NO

+    -