11 

Manual calculation of the sensor values 

The following formula can be used to evaluate the humidity sensor.  
VDD = operating voltage (5V), VAD = humidity sensor, analog value of the DS2438, Xsense = light sensor, 
analog value of the DS2438.   

 
Humidity calculation 

Offset = 0.847847 (Zero Offset V), slope  = 29.404604 (Slope: mV/ %RH) 
Srh = (VAD_new - offset) / (slope / 1000)    

 

 

 

 

 

 

rFH = (Srh + 2)/ ((1.0305 + (0.000044 * Temperature) - (0.0000011 * Temperature x 10²))))) 
 
for Loxone control: 
I1 = VAD-Value, I3 = Temperature 
((((5/I2*I1)-0,847847)/(29,404604/1000))+2)/((1,0305+(0,000044*I3)-(0,0000011*I3^2))) 

 
Brightness calculation 

Xsense in Volt, factor = 25600 
correction for operating voltage fluctuations: Xsense = (5 / VDD) * Xsense 
brightness (LUX) = (0,223V 

– Xsense) * factor 

 

12 

1-Wire Network, Cabling 

The special feature of the 1-Wire system is the "BUS technology". All devices (sensors and actuators) are 
operated in parallel on a three-wire line, which is used for both power supply and data communication. The  
1-Wire Bus system joins the list of other successful bus systems such as CAN or Modbus RTU. All of the 
installation principles recommended for these are also applicable and appropriate to 1-Wire.  
The maximum size of a 1-Wire Network is determined by various factors. These are mainly:  

Total cable length and cable type 

Number of 1-Wire devices 

Type of cable installation (topology) 

Number and design of cable connectors (unnecessary connection transitions should be avoided) 

All factors in total are summarised and designated as 1-Wire Bus load. Each increase in a factor increases the 
total 1-Wire Bus load for the 1-Wire Controller and thus reduces the maximum network size.

   

 

According to our many years of experience and a lot of feedback from customers, the following conservative 
recommendation can be made: 

Maximum cable length 50 -120m 

Number of 1-Wire devices no more than 20 -22 pieces 

As linear a topology as possible without T-junctions  

The topology in particular plays a major role. If possible, it should be installed in a linear topology. The linear 
topology can be compared like pearls on a pearl necklace. The data line should be laid from one device to the 
next without T-joints. 
Furthermore, the type of cable used can also be mentioned here. We recommend for the cabling  
CAT5 or CAT6 network cable. It is also possible to use J-Y(St)Y telephone cables and KNX cables. Longer 
cable runs are possible with CAT5 versus CAT7 cables. 
With twisted pair cables, a longer connection length can be achieved in an undisturbed environment, as the 
capacitive Bus load is lower. A total length of 50 m and more can be easily achieved without additional 
measures. 

Note on brightness measurement 

It should be noted that due to the placement of light sources in relation to the angle of incidence of the 
Multisensor, there may be considerable deviations in the measured brightness values compared to hand-held 
brightness meters. This is not a fault of the Multisensor.  
In the case of lighting with fluorescent or LED lamps, the value may also fluctuate. A living room brightness 
control is usually affected by strongly changing light conditions, e.g. by shadows of people in the room and 
the resulting fluctuations of the sensor light values, and a well-functioning control function is often difficult to 
implement. The reason for this is largely the unfavorable placement in the light switch area for the brightness 
measurement of the Multisensor. 
 

Содержание MS 100

Страница 1: ... 12 Bit resolution Light sensor for detection of ambient brightness Voltage monitoring integrated Equipped with original DS2438 chip Mounting on flush mounted boxes possible Universal surface mounting Shapely and high quality sensor housing with integrated ventilation slots Connection via screw terminals Simple power supply 5V Application Temperature sensor for individual room control Control sens...

Страница 2: ...ble from the ESERA website Calibration of the internal sensors is not necessary The device can be put into operation immediately without waiting time The electrical connection to the 1 Wire Bus system of the MS 100 is done with screw terminals and can be operated in standard mode with 3 cables for ground data and 5V Each MS 100 Multisensor has an individual serial number The Multisensor contains a...

Страница 3: ...arasitic mode is not supported MS 100 Multisensor Note The module may only be operated at the voltages and under the ambient conditions specified for it The modules may only be commissioned by a qualified electrician Please observe the specified operating position of the device For further information on the operating conditions see the following instructions under Operating conditions Due to the ...

Страница 4: ...et brightness Lux example 800 00 Lux For further information on the options and commands please refer to the current Programming Manual of the 1 Wire Controller 1 Wire Gateway which can be found within Config Tool 3 8 Integration in IP Symcon For the integration of the 1 Wire Controllers a suitable ESERA module for all sensors and controllers is available in the IP Symcon module store This can be ...

Страница 5: ...nated as 1 Wire Bus load Each increase in a factor increases the total 1 Wire Bus load for the 1 Wire Controller and thus reduces the maximum network size According to our many years of experience and a lot of feedback from customers the following conservative recommendation can be made Maximum cable length 50 120m Number of 1 Wire devices no more than 20 22 pieces As linear a topology as possible...

Страница 6: ...blies when it is certain that the devices are disconnected from the power supply and electrical charges stored in the components inside the device have been discharged Live cables or wires to which the device or an assembly is connected must always be tested for insulation faults or breaks If an error is detected in the supply line the device must be immediately taken out of operation until the fa...

Страница 7: ...ch ESERA GmbH is responsible and in the case of replacement goods the replacement is faulty the buyer has the right to have the original purchase price refunded or a reduction of the purchase price ESERA GmbH accepts liability neither for the constant and uninterrupted availability of the ESERA GmbH or for technical or electronic errors in the online offer We develop our products further and we re...

Отзывы: