Ambient conditions 

Temperature, 
operation 

-30°C to 60°C 

Air humidity 

10 - 92% (non condensing) 

Dimensions 

71 x 71 x 32mm (LxWxH) 

Protection class 

III 

Protection system 

IP20 

Auto-E-Connect 
Support 

No Auto-E-Connect Support 

 

Conformity 

EN 50090-2-2 
EN 61000-4-2, ESD 
EN 61000-4-3, HF 
EN 61000-4-4, Burst 
EN 61000-4-5, Surge 
EN 61000-6-1, Interference immunity 
EN 61000-6-3, Interference radiation 
RoHS 
 

Connection diagram 

The connection diagram is available in the store as a 
separate document. 
The Temperature and Humidity Sensor is connected by 
screw terminals.  
The pin assignment of the screw terminals is printed on the 
printed circuit board.  

 

Assignment 

The Multisensor has to be supplied with three cables 
(ground, 1-Wire Data and 5V). The parasitic mode is not 
supported. 
 
 
 

MS 100 

Multisensor 

Note 

The module may only be operated at the voltages and under the ambient conditions specified for it. 
The modules may only be commissioned by a qualified electrician.  
 
Please observe the specified operating position of the device. 
 
For further information on the operating conditions, see the following instructions under "Operating 
conditions".  
 
Due to the high quality reverse polarity and overvoltage protection no parasitic operation is possible. 
 

Note on brightness measurement 

Please note that due to the positioning of light sources in relation to the angle of incidence of the 
Multisensor, there may be considerable deviations in the measured brightness values of hand-held 
brightness meters. 
 
In the case of lighting with fluorescent or LED lamps, the value may also fluctuate. A living room brightness 
control is usually impaired by strongly changing light conditions, e.g. by shadows of people in the room and 
the resulting fluctuations of the sensor light values, and a well-functioning control function is often difficult to 
implement. The reason for this is largely the unfavorable placement in the light switch area for the 
brightness measurement of the Multisensor.   
   
 
 

Содержание MS 100

Страница 1: ... 12 Bit resolution Light sensor for detection of ambient brightness Voltage monitoring integrated Equipped with original DS2438 chip Mounting on flush mounted boxes possible Universal surface mounting Shapely and high quality sensor housing with integrated ventilation slots Connection via screw terminals Simple power supply 5V Application Temperature sensor for individual room control Control sens...

Страница 2: ...ble from the ESERA website Calibration of the internal sensors is not necessary The device can be put into operation immediately without waiting time The electrical connection to the 1 Wire Bus system of the MS 100 is done with screw terminals and can be operated in standard mode with 3 cables for ground data and 5V Each MS 100 Multisensor has an individual serial number The Multisensor contains a...

Страница 3: ...arasitic mode is not supported MS 100 Multisensor Note The module may only be operated at the voltages and under the ambient conditions specified for it The modules may only be commissioned by a qualified electrician Please observe the specified operating position of the device For further information on the operating conditions see the following instructions under Operating conditions Due to the ...

Страница 4: ...et brightness Lux example 800 00 Lux For further information on the options and commands please refer to the current Programming Manual of the 1 Wire Controller 1 Wire Gateway which can be found within Config Tool 3 8 Integration in IP Symcon For the integration of the 1 Wire Controllers a suitable ESERA module for all sensors and controllers is available in the IP Symcon module store This can be ...

Страница 5: ...nated as 1 Wire Bus load Each increase in a factor increases the total 1 Wire Bus load for the 1 Wire Controller and thus reduces the maximum network size According to our many years of experience and a lot of feedback from customers the following conservative recommendation can be made Maximum cable length 50 120m Number of 1 Wire devices no more than 20 22 pieces As linear a topology as possible...

Страница 6: ...blies when it is certain that the devices are disconnected from the power supply and electrical charges stored in the components inside the device have been discharged Live cables or wires to which the device or an assembly is connected must always be tested for insulation faults or breaks If an error is detected in the supply line the device must be immediately taken out of operation until the fa...

Страница 7: ...ch ESERA GmbH is responsible and in the case of replacement goods the replacement is faulty the buyer has the right to have the original purchase price refunded or a reduction of the purchase price ESERA GmbH accepts liability neither for the constant and uninterrupted availability of the ESERA GmbH or for technical or electronic errors in the online offer We develop our products further and we re...

Отзывы: