esera automation ECO 208 PRO Скачать руководство пользователя страница 3

 

 
 

 Art.No.11603-48  

 

*

 

if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator. 

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of 
ESERA GmbH. Errors and technical modification subject to change. 



ESERA GmbH 2021 

www.esera.de 

11603-48  V1.0 R1.1 Manual 

Page 3 of 18 

Auto-E-Connect Support 

The ECO 208 PRO 1-Wire Controller supports Auto-E-Connect Level I, II and III.  
 

Auto-E-Connect System 

With the launch of the ECO Controller, the ESERA Auto-E-Connect® 1-Wire Plug and Play system for the  
1-Wire Bus is now introduced and supported.  
This means that fully automatic configurations of the 1-Wire devices* (sensors and actuators) are now 
possible on the 1-Wire Bus. It is optimised for commercial and industrial applications and enables significant 
added value beyond sensor and chip data. 
 
The Auto-E-Connect function is built up in three levels. Currently there are Level I, Level II and Level III  
available. 
 
With Auto-E-Connect Level III, fully automatic configurations of the 1-Wire devices on the  
1-Wire Bus are possible. It is optimised for industrial and IoT applications and enables significant added 
value beyond sensor and chip data. 
With the Auto-E-Connect function, ESERA devices are recognised fully automatically, suitable libraries are 
started and ready-formatted data is output. 
The Auto-E-Connect functionality will be available for the ECO Controller and ESERA-Station 200 Pro from 
2021. 
 

Auto-E-Connect Level I 

OWD Detect

: Detection of new sensors* and actuators* and automatic start of adapted libraries 

 

Auto-E-Connect Level II 

Visualise product data

:  Readout and visualisation of Auto-E-Connect and manufacturer data of sensors* and 

actuators*, such as article number, date of manufacture, firmware and hardware version. 
  

Auto-E-Connect Level III 

Extended Plug and Play System for 1-Wire Bus 

o

 

Pre Configuration

: The OWD number for the next installation can be written into the 1-Wire device*. 

o

 

Automatic Positioning

: The device* logs on to each ECO controller with Auto-E-Connect III with the new 

desired OWD number. This automatic registration works up to the maximum possible OWD number of the 
ECO Controller. 

o

 

Sensorfinder Function

: The ECO 208 PRO can activate a status LED within the ESERA 1-Wire Pro 

sensors*. The status LED flashes or lights up permanently for a certain time. This makes the detection of a 
device in a 1-Wire Network much easier. Faster detection saves a lot of time and therefore money when 
searching for a 1-Wire device. 

o

 

Classes Assignment

: ESERA 1-Wire devices are assigned to OWD classes with the same properties. This 

assignment enables fully automatic visualisation and data evaluation in control systems. A class list is 
available from ESERA.  
 

For further information on the ESERA Auto-E-Connect system, please refer to the ESERA website and the 
ESERA Config Tool 3. 
Auto-E-Connect is registered by ESERA GmbH as a German and European Patent. 
 
 
 
 
 
 
 

 

Содержание ECO 208 PRO

Страница 1: ...relay output alarm output Plug and Play interface for up to 30 sensors e g temperature humidity air quality gas sensors Web server for configuration Debug and Firmware updates robust industrial design extensive software support power supply 48VDC Auto E Connect Support Level I to III Fast readout of all 1 Wire Devices in a 1 2 seconds cycle Basic unit for many industrial and telecommunication solu...

Страница 2: ...1 Wire devices The ECO 208 PRO independently scans the 1 Wire Network for new 1 Wire devices reads their Auto E Connect data automatically adapts the device libraries and outputs the adapted data in plain text adapted to the scanned 1 Wire devices Designed for all 1 Wire Networks The 1 Wire interface of the ECO 208 PRO is specially designed to safely operate small up to very large 1 Wire Networks ...

Страница 3: ...eady formatted data is output The Auto E Connect functionality will be available for the ECO Controller and ESERA Station 200 Pro from 2021 Auto E Connect Level I OWD Detect Detection of new sensors and actuators and automatic start of adapted libraries Auto E Connect Level II Visualise product data Readout and visualisation of Auto E Connect and manufacturer data of sensors and actuators such as ...

Страница 4: ...g in terminals up to 2 5qmm cable cross section Output voltage 5V 10 max 300mA overload overvoltage and short circuit proof Isolation Galvanic isolation between Ethernet and 1 Wire Interface Supported DS2401 DS1963 DS1990 DS1820 DS18S20 DS18B20 DS2413 DS2438 DS2450 1 Wire devices DS2408 DS2405 DS2406 only input DS2423 other chips on request We will be happy to support other components as an OEM pr...

Страница 5: ...Errors and technical modification subject to change ESERA GmbH 2021 www esera de 11603 48 V1 0 R1 1 Manual Page 5 of 18 LED Green WLAN WLAN Network Status LED lights up when a WLAN Network connection is established flashes when the WLAN access point is activated and a direct connection is possible 8 Connection plan Module top side Digital inputs normally open contacts Reset Button Reset Button for...

Страница 6: ...et button of the system When the button is pressed the unit is restarted The stored data is retained but all connections are Interrupted This keystroke does not correspond to an interruption of the power supply Note The module may only be operated at the voltages and under the ambient conditions specified for it The operating position of the unit is arbitrary The modules may only be put into opera...

Страница 7: ...sensor or actuator All rights reserved Reproduction as well as electronic duplication of this user guide complete or in part requires the written consent of ESERA GmbH Errors and technical modification subject to change ESERA GmbH 2021 www esera de 11603 48 V1 0 R1 1 Manual Page 7 of 18 10 Connection example 1 Wire Multisensors ...

Страница 8: ...n also communicate at any time with any terminal program e g z B Hercules oder Putty via UDP TCP IP to exchange data with the ECO 208 PRO and to carry out the configuration Details on the communication commands can be found in the document Programming Manual which you can find in the download area of the ECO 208 PRO and within the Config Tool 3 software 12 1 ESERA ASCII Textprotokoll The ECO 208 P...

Страница 9: ...und in the Programming Manual in the download area of the ECO 208 PRO and within the Config Tool 3 software Excerpt Modbus adress description Description Read address Number of words 16Bit Data type Gateway No 60000 1 Word Article No 60001 1 Word Firmware Version 61000 4 String Hardware Version 61010 3 String Serial number 61020 9 String Time 61030 4 String Date 61035 4 String 1 Wire Bus Sensors a...

Страница 10: ... LAN and WLAN The ECO Controller with Maxi interface logs into your network with the identifier ESERA The Ethernet interface is set to DHCP in the delivery state 14 2 Web server LogIn Password LogIn In order to be able to log into the web server of the ECO Controller use the following password for the initial login eserapwd For security reasons the password is not displayed in plain text but with ...

Страница 11: ... 2 5 In this menu you can set the port number of the Modbus TCP interfaces for example Disable AP Modus This button is only visible if the access point is activated To deactivate the WLAN access point press the Disable AP Mode button or press the WLAN Mode button at least 3 seconds on the front panel of the unit If the access point is not activated this button is not visible You can only activate ...

Страница 12: ...mask and the gateway IP address are set here TCP Server or UDP operating mode With this selection the basic operating mode for the ECO Controller Maxi Interface is set Port The port address is assigned for socket 1 the ESERA ASCII protocol The port can be selected in the range 1 50000 The default port is 5000 DHCP Manual Operating mode IP address assignment You can choose between automatic DHCP an...

Страница 13: ...protocols can be integrated here and made selectable We will be happy to provide you with an offer for the integration of further protocols Protocol and Port for Socket Data connections Interface 1 ASCII Protocol Interface 1 is permanently reserved for a TCP IP or UDP socket data connection via ESERA ASCII text protocol The port for this interface is set on the Interface Settings page Interface 2 ...

Страница 14: ...surface To activate the access point press the WLAN Mode button for approx 3 seconds Activation is confirmed by the LED and the display Now you can connect to the ECO Controller using a WLAN capable device with a web browser To do this select the access point ESERA The web server of the ECO Controller can be reached via the IP address 192 168 4 1 A data connection via ESERA ASCII and Modbus TCP ca...

Страница 15: ...r and thus reduces the maximum network size According to our many years of experience and a lot of feedback from customers the following conservative recommendation can be made Maximum cable length 50 120m Number of 1 Wire devices no more than 20 22 pieces As linear a topology as possible without T junctions The topology in particular plays a major role If possible linear topology should be used T...

Страница 16: ...we will be happy to help you Simply contact our support team by e mail at support esera de 17 Example for integration in Codesys We would be pleased to provide you with a test software for the integration of the ECO 208 PRO into the PLC software Codesys Please contact our technical support under support esera de 18 Example for integration in Siemens SPS For many years the Modbus TCP protocol has a...

Страница 17: ... that the devices are disconnected from the power supply and electrical charges stored in the components inside the device have been discharged Live cables or wires to which the device or an assembly is connected must always be tested for insulation faults or breaks If an error is detected in the supply line the device must be immediately taken out of operation until the faulty cable has been repl...

Страница 18: ...o have the original purchase price refunded or a reduction of the purchase price ESERA GmbH accepts liability neither for the constant and uninterrupted availability of the ESERA GmbH or for technical or electronic errors in the online offer We develop our products further and we reserve the right to make changes and improvements to any of the products described in this documentation without prior...

Отзывы: