3.2.3 Setting the Module Number
When the configuration has been successful, the module number (Node-ID) has to be set by means of
the rotary switches before the module is switched on, i.e. before power is supplied.
The module number can be set to values between 1 and 127 (01h to 7Fh).
The CAN-CBM-REL4 module wakes up in the CANopen-defined status
pre-operational
and reports
this by transmitting the boot-up protocol on the CAN bus.
If the CAN-CBM-REL4 module was started with a module number outside of the permissible range,
the red LED flashes 4x in succession (see page 8). The green LED is off.
As long as the module number is not within the defined range, the CAN-CBM-REL4 module does not
get into the
pre-operational
status.
In order to correct the module number you have to disconnect the module from the power supply, set
the new module number and connect the power supply again. Then the CAN-CBM-REL4 module wakes
up
pre-operational
and the green LED flashes constantly.
The module is shipped with the module number (Node-ID) set to 01