3. Configuration via Rotary Switches
Depending on the setting of the two rotary switches LOW (SW110) and HIGH (SW111), the CAN-
CBM-REL4 module starts with different configuration:
Default configuration
00h :
Default configuration is stored in EEPROM
Manual configuration
FFh:
Parameters are selected and configured via the rotary
switches, configuration is stored in EEPROM
When the configuration has been finished, the module number is set via both rotary switches:
Setting the module number
01-7Fh: CAN-CBM-REL4 module is started with the configuration
presently stored in the EEPROM. The module number
corresponds to the current position of the rotary switches
when the module is switched on and is not to be changed
during operation. The module is shipped with the module no.
set to 01h.
Note:
If switching the module OFF and ON, you have to wait a few seconds between switching
ON and switching OFF, because the capacitors of the local power control must be
discharged!