4. Pre-Installation 

Prior to installation, manifold configuration must be determined as left or right handed.

5. Installation

5.1

 Carefully remove from the packaging and check that all components are in place and that  

 

nothing has been damaged during delivery.

5.2

  The pump mixer is supplied for connection to the right-hand side of the manifold but can  

 

be altered very simply for connection to the left-hand side. (See above)

5.3

  To change orientation: 

 

a) Remove swivel nut (7) from the TMV and move to opposite connection.  

 

  (These joints use o-ring seals and should not be overtightened) 

 

b) Loosen the pump rotating nuts (5) on the elbow (6) and rotate through 180 degrees.  

 

  Re-tighten nut (5) after rotation. 

5.4

  Pipe connection orientation can be altered to suit using flow / return elbow (3) (supplied  

 

loose) fitted in either flow or return. 

5.5

  A swivel joint is fitted to each side of the control group for connecting to the 1” F manifold  

 tappings.

 

Carefully offer up and screw the swivel joint threads evenly into the    

 

 

manifold using a 37mm A/F spanner: the use of a 31mm A/F spanner will also ensure  

 

that the connection to the pump mixer is kept tight. The joints use o-ring seals and care  

 

should be taken not to over-tighten them.

5.6

  Once connected, finish securing the manifold and large area mixer to the wall if not    

 

already completed.

5.7

  The primary flow and return pipework can now be connected to the 2 x 3/4” F connections.  

 

The flow connection is at the H and the return connection is at the R. It is recommended  

 

that ball valves are used to isolate this pipework where it is connected to the pump mixer. 

Содержание T4

Страница 1: ...For underfloor heating with thermostatic mixing valve ESBE T4 Pump Control Set Installation and Commissioning Manual ...

Страница 2: ...le swivel joints for fast connection to 1 Female manifold tappings Nickel plated for improved appearance In built non return valve in flow elbow to enable simple system filling when commissioning 3 4 Female BSP flow and return connections Suitable for any manifold with connections on 210mm centres Also available in 200 and 225mm Fully reversible offering with side or bottom entry primary connectio...

Страница 3: ...imary connections can be applied from the side or bottom of the control pack 2 Connections Dimensions 3 Technical Data Maximum static pressure 10 Bar Maximum differential pressure 3 Bar Maximum temperature 95 C Operating temperature range Adjustable between 20 C to 55 C BS2164 Inlet connections 2 x 3 4 BSPF Outlet connections 2 x 1 BSPM swivel joint Overall dimensions mm 290 h x 150 w x 140 h Excl...

Страница 4: ... 4 Pipe connection orientation can be altered to suit using flow return elbow 3 supplied loose fitted in either flow or return 5 5 A swivel joint is fitted to each side of the control group for connecting to the 1 F manifold tappings Carefully offer up and screw the swivel joint threads evenly into the manifold using a 37mm A F spanner the use of a 31mm A F spanner will also ensure that the connec...

Страница 5: ...en select the desired pump setting The ESBE T4 control pack comes pre assembled ready for installation please ensure the pump connections are tightened before commissioning These connections are equipped with EPDM seals 7 Pump Settings Buttons All pump functions can be controlled with two buttons The button switches the night reduction function on and off The button controls the operating modes Th...

Страница 6: ...ure it against neing switched on again by unauthorized persons At high water temperatures and system pressures wait for the pump to cool down beforehand There is risk of burns Control panel and LED display 1 Display of energy consumption in watts 2 Automatic night reduction display 3 Button for activating the automatic night reduction 4 Operating mode selection button 5 Display for activated AUTO ...

Страница 7: ...t is suitable for use with floor areas of 60 90sqm or max output of 5kW Heat Pump Pack The heat pump model is a pre assembled unit that is designed to be connected via ball valves to the manifold The unit is for use in applications where water temperature controls are not required This is typically seen where heat pumps or low temperature systems are utilised The unit includes an A rated energy ef...

Страница 8: ......

Отзывы: