background image

4 (32)

MULTIPLE INSTALLATIONS OF CIRCULATION UNITS ON THE WALL

If more than one Circulation Unit should be used we recommend the use of Serie 
ESBE GMA manifold, with or without hydraulic separator. 
When no storage tank or other components performing a hydraulic separation 
are used, then manifold series GMA2XX should be installed. 

.

 

   ELECTRIC INSTALLATION

Electric connection of the Circulation Unit depends both on the circulation pump, 
actuator and /or controller. 

CIRCULATION PUMP 230 VAC, 50HZ:
The circulation pump should be preceded by a multi-pole contact breaker in the 
fixed installation. Earth-connection should not be broken.

L

N

You find more information about the circulation pump on  www.esbe.eu.

ACTUATOR:

Actuators supplied with 230 VAC should  be preceded by a mulitipole contact 
breaker in the fixed installation.

                 

M

You find more information about the actuator on www.esbe.eu.

IF USING LARGER SYSTEMS/CENTRAL REGULATING 

Read each product´s instruction manual.

 

  COMMISSIONING CIRCULATION UNIT

 

WARNING!

 

Before any intervention disconnect the electric mains through the 

external mounted switch and depressurise!

 

WARNING! 

Depending on the operating status of the circulation pump or 

system (fluid temperature), the entire Circulation Unit can become very hot. 

Both primary and secondary loops have to be washed in order to remove any 
possible mounting residuals.

Check that all connections are fully tightened: it´s important to check all 
connections before filling the system in order to avoid leakages or sprays which 
may be dangerous for the electric components. Open all shut-off valves and fill 
the primary and secondary loop following the instructions for the tank, boiler etc. 
During the filling phase recheck that all connections are tightened. 

FILLING AND VENTING

Fill the buffer tank and the primary loop with an appropriated liquid, according 
to the system instructions, respecting the limits of the components used. While 
filling the device, open any vents situated in the circuit. Watch the system until 
it reaches its correct operation condition. If pressure is not enough, adjust the 
pressure by repeating the above procedure.

To avoid problems with cavitation, fill up the system to get sufficient pressure 
head on the suction side of the circulation pump. The minimum pressure needed 
depends on the temperature of the fluid. Recommended min pressure head at 
fluid temperatures 50/95/110°C is 0,5/4,5/11 m respectively.

To make the filling and venting of the system easier it´s possible to force the check 
valve on the return side of the unit, to an open position (default), see Fig. 1.

 

After a complete filling and venting, turn the screw on the check valve back to it´s 
normal operating position, picture 2 and set the circulation pump operation to 
recommended position.

 

   HYDRAULIC INSTALLATION

SINGULAR INSTALLATION ON THE WALL 

Install the appliance on a solid wall.
1. Choose the correct position for the piping and drilling by usage of the Mounting 
template supplied with the package. Drill the holes in the wall for your installation 
purposes. Take care not to damage any electrical wiring or existing piping. 
2. Detach parts of the Circulation Unit's insulation shell.
The actuator/controller might be dismounted from the valve to give more space 
for the installation tools. Do not change the shaft position of the valve.
3. Mount the Circulation Unit on the wall with the supplied screws and plugs. 
Ensure that the pipes are completely in line and lock them firmly.

 

*Please note 

that to achive best performance there should be no tilt at all. 

 

WARNING!

 

For all installations, verify that the plugs are suitable for the kind of 

wall chosen. Otherwise replace them with a special model. To value the suitability of 
the plugs please consider the structure of the wall, all the units connected and the 
weight of the water. 

4. Connect the pipings. 

 

WARNING!

 

Equipment might be damaged when incorrect usage of tools.

5. Remount the insulation shell parts (and actuator/controller). 
 

GDF100

180˚

>

180˚

>

40 - 50 Nm

GRF100

GFF100

*

Содержание 61200100

Страница 1: ...ESBE SYSTEM UNITS CIRCULATION UNIT FLEXI Mtrl nr 9814 09 43 Ritn nr 7574 utg D Rev 1704 CIRCULATION UNIT FLEXI GB ...

Страница 2: ...schematics are general representations The producer won t be responsible for damages caused by wrong usage or unrespect of the instructions given in this manual The mounting of the unit must be performed by a qualified professional and in compliance with local regional laws This manual refers to standard products Different versions or functions are available At mounting pay attention and follow co...

Страница 3: ...3 32 MOUNTING POSSIBLE INSULATION ADJUSTMENTS EXAMPLE OF PUMP INSTALLATION LEFT RIGTH TRANSITION ...

Страница 4: ... the components used While filling the device open any vents situated in the circuit Watch the system until it reaches its correct operation condition If pressure is not enough adjust the pressure by repeating the above procedure To avoid problems with cavitation fill up the system to get sufficient pressure head on the suction side of the circulation pump The minimum pressure needed depends on th...

Страница 5: ... be kept HOW TO USE THE INFORMATION LEAFLET The Circulation Unit is equipt with an information display containing a leaflet that graphically explains what kind of application the unit is controlling It gives you also the possibility to write in notes and leave your business card behind Just remove the display glass and select the suitable information MAINTENANCE The circulation unit does not requi...

Страница 6: ...gsgemäßem Gebrauch oder Nichtbeachten der Anweisungen in dieser Einbauanleitung ergeben Die Montage muss von geeignetem Fachpersonal unter Beachtung lokaler und regionaler Bestimmungen und Vorschriften erfolgen Diese Einbauanleitung beschreibt Standardprodukte Abweichende Serien oder Funktionen sind erhältlich Gehen Sie bei der Montage konzentriert und umsichtig vor beachten Sie allgemein übliche ...

Страница 7: ...7 32 MONTAGE ANPASSEN DER ISOLIERSCHALEN EINBAU DER UMWÄLZPUMPE UMBAU VORLAUF RECHTS AUF VORLAUF LINKS ...

Страница 8: ...e Entlüftungseinrichtungen Beobachten Sie das System bis alle Luft entwichen ist und der ordnungsgemäße Betriebsdruck erreicht ist Um Probleme durch Kavitation zu vermeiden füllen Sie das System soweit auf dass Sie auf der Ansaugseite der Umwälzpumpe einen ausreichenden Betriebsdruck erhalten Der benötigte Mindestdruck ist abhängig von der Temperatur der Flüssigkeit Der empfohlene minimale Betrieb...

Страница 9: ...Die Temperaturangaben sind nur Referenzwerte und können unter bestimmten Umständen variieren Der Temperaturbereich wird jedoch eingehalten KENNZEICHNEN DER PUMPENGRUPPE Sie haben die Möglichkeit die Pumpengruppe mit dem jeweiligen Anwendungssymbol zu kennzeichnen Außerdem können Sie Ihre Visitenkarte oder Notizen hinterlegen Entfernen Sie hierzu die Abdeckung und wählen Sie die entsprechenden Info...

Отзывы: