4 INSTALLATION
0459 293 787
- 17 -
© ESAB AB 2018
Check that the unit is connected to the correct mains power supply
voltage, and that it is protected by the correct fuse sizes.
A protective earth connection must be made, in accordance with
regulations.
Rating plate with supply connection data
Recommended fuse sizes and minimum cable areas
Mig 5000i
460 V 3~ 60 Hz
Mains voltage
460 V
Mains cable area,
CU/AWG (mm
2
)
4G6
Phase current, I
RMS
28 A
Fuse
Time Delay
50 A
NOTE!
Sizes per National Electric Code for 90 °C rated copper conductors @ 30 °C
ambient. Not more than three conductors in raceway or cable. Local codes
should be followed if they specify larger sizes other than those listed above.
4.4
Terminating resistor
In order to avoid communication interference,
the ends of the CAN bus must be fitted with
terminating resistors.
One end of the CAN bus is at the control
panel, which has an integral terminating
resistor. The other end at the power source
must be fitted with the terminating resistor, as
shown on the right.