#550 DIGITAL INSULATION TESTER 

INSTRUCTION MANUAL

 

 

SAFETY INFORMATION 

Read the following safety information carefully before attempting to operate or service the meter. 
To  avoid  damaging  the  instrument,  do  not  apply  signals  which  exceed  the  maximum  limits  shown  in  the 
technical specifications tables. 
Do not use the meter or test leads if they look damaged.  Use extreme caution when working around bare 
conductors or bus bars. 
Accidental contact with the conductor could result in electric shock. 
Use  the  meter  only  as  specified  in  this  manual;  otherwise,  the  protection  provided  by  the  meter  may  be 
impaired. 
Read the operating instructions before use and follow all safety Information. 
Caution when working with voltages above 60V DC or 30V AC RMS. Such voltages pose a shock hazard. 
Before taking  resistance measurements  or  testing acoustic continuity, disconnect  circuit from  main power 
supply and all loads from the circuit. 

 

Safety symbols:   

Caution refer to this manual before using the meter. 
 

Dangerous voltages. 

 

Meter is protected throughout by double insulation or reinforced insulation. 

When servicing, use only specified replacement parts. 

CE

 Comply with EN-61010-1 

 

1.  SPECIFICATIONS 
1-1 General Information 

Environment conditions:   

Installation Categories II 

Pollution Degree 2 

Altitude up to 2000 meters 

Indoor use only 

Relatively humidity 80% max. 

Operation Ambient 0~40ºC 

Maintenance & Clearing:   

Repairs or servicing not covered in this 

manual should only be performed by qualified personnel. 

Periodically wipe the case with a dry cloth. Do not use abrasives or solvents on this 

instrument. 

Display:       

  Large LCD with dual display   

Measurement Range:      200

Ω

, 200k

Ω

, 200M

Ω

/250V, 200M

Ω

/500V, 

2000M

Ω

/1000V, 750V/ACV, 1000V/DCV. 

Sampling Rate:       2.5 times per second. 
Zero Adjustment:       

Automatic adjustment. 

Over Range Indicator:      Number 1 of highest digit is displayed. 
Low Battery Indication:      The “      “ symbol is displayed when the battery 

voltage becomes too low. 

Operating Temperature:    0ºC to 40ºC (32ºF to 104ºF) 

Содержание 550

Страница 1: ... continuity disconnect circuit from main power supply and all loads from the circuit Safety symbols Caution refer to this manual before using the meter Dangerous voltages Meter is protected throughout by double insulation or reinforced insulation When servicing use only specified replacement parts CE Comply with EN 61010 1 1 SPECIFICATIONS 1 1 General Information Environment conditions Installatio...

Страница 2: ...Overload Protection 200Ω 0 1 Ω 4 5V 200k Ω 0 1k Ω 1 2 3 0V 250Vrms Continuity Beeper Range Resolution Operation Resistance Max open Circuit Voltage Overload Protection 0 1 Ω Resistance 40Ω 4 5V 250Vrms Short circuit current 200mA DC Voltage Range Resolution Accuracy Input Impedance Overload Protection 1000V 1V 0 8 3 10MΩ 1000Vrms AC Voltage 40Hz 400Hz Range Resolution Accuracy Input Impedance Over...

Страница 3: ...connected The indicator should read 00 0 Ω When the leads are not connected the display will read infinity indicated by 1 This will ensure that test lead are in good working condition 4 INSULATION RESISTANCE MEASUREMENTS a Measurements at 200M Ω 250V This is the voltage used for the majority of insulation resistance tests on normal installation requirement To measure insulation resistance press th...

Страница 4: ...tely 40 Ω it will be indicated by a continuous beep 6 AC DC VOLTAGE MEASUREMENTS a Set the range switch to ACV or DCV position b Connect red test lead to V Ω terminal and black test lead to terminal COM b Connect test prods of test leads IN PARALLEL to the circuit being measured c Read the voltage value on LCD 7 POWER TOOLS AND SMALL APPLIANCES This test would also apply to other similar equipment...

Страница 5: ...lead sheath by connecting one megohmmeter lead to a ground and or lead sheather and the other megohmmeter lead to each of the conductors in turn Check insulation resistance between conductors by connecting megohmmeter leads to conductors in pairs For after sale service please send to Electronic Specialties Inc 139 Elizabeth Ln Genoa City WI 53128 Phone 262 279 1400 Fax 262 279 1300 For more qualit...

Отзывы: