14
DIP
Modes and functions
Option
Effect
DIP1
OFF
DIP2
Advance warning
ON
the flashing light comes on and the operation begins after a 3
second warning
OFF
the flashing light comes on and the operation begins
immediately
DIP3
Opening mode
ON
step-by-step opening (the gate halts if a key command is
activated during opening, and closes if activated again)
OFF
collective opening (the control board does not obey the key
commands during opening)
DIP4
Automatic or step-by-step mode
(for pedestrian and total operation)
ON
automatic mode (the gate closes automatically after the
standby time has passed, which is adjusted using T.E.)
OFF
step-by-step mode (the gate only closes when receiving the key
command)
DIP5
Automatic mode optional
(only if DIP4 = ON)
ON
during standby, the gate obeys the key commands (this can be
closed before standby time finishes)
OFF
the gate cannot be closed until standby time finishes; a key
command (or photocell activation) will cause standby time to
restart
DIP6
Opening photocell testing
ON
testing enabled
OFF
testing disabled
DIP7
Reserved for future upgrades
ON
always place in OFF
OFF
always place in OFF
DIP8
Reserved for future upgrades
ON
always place in OFF
OFF
always place in OFF
DIP9
Closing photocell testing
ON
testing enabled
OFF
testing disabled
DIP10
Reserved for future upgrades
ON
always place in OFF
OFF
always place in OFF
KM1800: function and mode selection using SW2 (DIP1 = OFF)
T.LG: garage light time
If the garage lighting circuit has been connected to the
control panel, regulate the time which the lights shall
remain on using T.LG.
•
Minimum value: 3 seconds; maximum value: 90
seconds
T.E: gate open standby time
If automatic functioning mode has been programmed
(DIP4=ON), set T.E. to adjust standby time with the gate
open (before automatic closing begins).
•
Minimum value: 0 seconds; maximum value: 90
seconds
P.M: motor torque
Adjust P.M at its maximum value, since the operator has a
mechanical clutch for torque adjustment.
KM1800: potentiometer adjustment