DIP

Modes and functions Option

Effect

DIP1

Soft start-up

ON

no soft-startup

OFF

with soft-startup.

DIP2

Limit Switches

ON 

Limit Switches normally closed

OFF

Limit Switches normally open

DIP3

 and 

DIP4

Automatic mode 

or 

step-by-step mode

DIP3=OFF and DIP4=OFF

step-by-step mode (the gate only closes when receiving
the key command)

DIP3=OFF and DIP4=ON

12s automatic mode (the gate closes automatically after
a 12-second standby)

DIP3=ON and DIP4=OFF

24s automatic mode (the gate closes automatically after
a 24-second standby)

DIP3=ON and DIP4=ON

36s automatic mode (the gate closes automatically after
a 36-second standby)

DIP5

Encoder

ON

encoder disabled 
(does not perform soft-stop or obstacle detection)

OFF

encoder enabled

Function and mode selection using SW1

E287L

5

VR1: Sensitivity in detecting obstacles

The operator has an encoder to detect obstacles and
prevent collisions. Sensitivity in detection can be adjusted
using this potentiometer. 

Turning the potentiometer clockwise decreases sensitivity;
turning it anti-clockwise increases it.

VR2: Braking time

The motor is used to brake at the end of the operation, thus
offsetting the inertia of the gate when braking. 
Adjust the potentiometer to ensure proper braking.

Turning the potentiometer clockwise increases the force;
turning it anti-clockwise decreases it. 

VR3: Soft-stop distance

Soft-stop adjustment, where the operator moves at slow
speed before reaching the stopper.

Turning the potentiometer clockwise increases the
distance; turning it anti-clockwise decreases it.

VR4: Operator force

Torque or force exerted by the operator during the
operation. To ensure safety for people, adjust the force at
the lowest value compatible with good operation of the
facility.

Turning the potentiometer clockwise increases the force;
turning it anti-clockwise decreases it.

Torque adjustment, respecting the maximum
closing forces set out in Standard EN12453:2000.
Make the readings as described in Standard EN
12445:2000.

SW1

VR1

VR2

VR3

VR4

P287M

Potentiometer adjustment

Содержание CAT

Страница 1: ...r upgrades being included as a result of new versions which are not necessarily compatible with previous ones For this reason some options or functions may differ or be unavailable if your firmware is older than shown in this guide 90º 90º D287A 90 135 200 5 130 200 FCC FCA E287C Assembly levels mm Manual operation Motorised operation locking Proceed in reverse order to release Move the gate manua...

Страница 2: ... F1 10A fuse Ensure the power supply is disconnected before making or changing the connection When the connections are complete return the control panel cover The panel has a built in radio receiver RSD to receive transmitter signals at 433 92MHz Connectors CLOSE 1 Close Pushbutton OPEN 2 Open Pushbutton STOP 3 Stop Pushbutton COM 4 Pushbutton Common A T 5 Total Opening Pushbutton A P 6 Pedestrian...

Страница 3: ...he fourth channel button although it does not need to be programmed when programming total opening buttons 1 2 or 3 number 4 is automatically assigned to pedestrian opening R287C Carry out the same process to programme more transmitters if required The memory can be used with up to 25 transmitters Deleting all the transmitters 1 Connect the electrical power supply 2 Press S1 until the LEARN LED co...

Страница 4: ...can be adjusted using this potentiometer Turning the potentiometer clockwise decreases sensitivity turning it anti clockwise increases it VR2 Braking time The motor is used to brake at the end of the operation thus offsetting the inertia of the gate when braking Adjust the potentiometer to ensure proper braking Turning the potentiometer clockwise increases the force turning it anti clockwise decre...

Отзывы: