82
Gr. 5Gr. 5Gr. 5Gr. 5Gr. 5
- Integral preload of the first PID group
- Integral preload of the first PID group
- Integral preload of the first PID group
- Integral preload of the first PID group
- Integral preload of the first PID group
- [r.d13]
- [r.d13]
- [r.d13]
- [r.d13]
- [r.d13]
This parameter is available when at least one control output is
configured, "Pb" [r.d01] is different from 0 and the instrument is
in programmer mode.
Lower display: IP x where x is the number of the selected PID
group.
Ranges:
- from 0.0 to 100.0 % of the output when device is configured
with only one control output
- from -100.0 to 100.0 % of the output when device is
configured with two control outputs (split range excluded)
- Relative secondary output gain of the first
- Relative secondary output gain of the first
- Relative secondary output gain of the first
- Relative secondary output gain of the first
- Relative secondary output gain of the first
PID group - [r.d14]
PID group - [r.d14]
PID group - [r.d14]
PID group - [r.d14]
PID group - [r.d14]
This parameter is available when two control outputs are
configured (split range excluded), "Pb" [r.d01] is different from 0
and the instrument is in programmer mode.
Lower display: r.Gnx where x is the number of the selected PID
group.
Range: from 0.20 to 2.00
- Overlap/dead band between main and
- Overlap/dead band between main and
- Overlap/dead band between main and
- Overlap/dead band between main and
- Overlap/dead band between main and
secondary outputs of the first PID group
secondary outputs of the first PID group
secondary outputs of the first PID group
secondary outputs of the first PID group
secondary outputs of the first PID group
- [r.d15]
- [r.d15]
- [r.d15]
- [r.d15]
- [r.d15]
This parameter is available when two control outputs are
configured (split range excluded), "Pb" [r.d01] is different from 0
and the instrument is in programmer mode.
Lower display: OLPx
where x is the number of the
selected PID group.
Range: from -20 to 50
NOTE
NOTE
NOTE
NOTE
NOTE: A negative value means a dead band while a positive
value means an overlap.
NOTE
NOTE
NOTE
NOTE
NOTE: For PID group 2 to 5, the instrument will show on the
lower display the respective PID group number and it is
possible to perform the same setting described for PID group 1.
- Group 4 default data loading - [r.d16]
- Group 4 default data loading - [r.d16]
- Group 4 default data loading - [r.d16]
- Group 4 default data loading - [r.d16]
- Group 4 default data loading - [r.d16]
Range: OFF = No loading data
ON = Loading data
Gr. 4Gr. 4Gr. 4Gr. 4Gr. 4
XKP-1-D1.pmd
25/05/2006, 11.28
82