MOUNTING REQUIREMENTS
MOUNTING REQUIREMENTS
MOUNTING REQUIREMENTS
MOUNTING REQUIREMENTS
MOUNTING REQUIREMENTS
This instrument is intended for permanent installation,
for indoor use only, in an electrical panel which
encloses the rear housing, exposed terminals and
wiring on the back.
Select a location, for instrument mounting, where
minimum vibrations are present and the ambient
temperature is within 0 and 50 °C (32 and 122 °F).
The instrument can be mounted on a panel up to 15
mm thick with a cutout of 92 x 45 mm (PKP) or 92 x
92 mm (MKP).
For outline and cutout dimensions refer to Fig. 2.
The surface texture of the panel must be better
than 6,3
µ
m.
The instrument is shipped with rubber panel
gasket.
To assure the IP65 and NEMA 4 protection, insert
the panel gasket between the instrument and the
panel as shown in fig. 1.
While holding the instrument against the panel
proceed as follows:
1) insert the gasket in the instrument case;
2) insert the instrument in the panel cutout;
3) pushing the instrument against the panel;
4) insert the mounting brackets as shown in fig.1;
Fig. 1
Gasket
bracket
bracket
Panel
Screw
Panel
Screw
brackets
Gasket
5) with a screwdriver, turn the screws with a torque between
0.3 and 0.4 Nm.
Screws
XKP-1-D1.pmd
25/05/2006, 11.28