GB-17
D
GB
F
NL
I
E
Technical data
Inlet pressure p
u
:
natural gas: 20 – 25 mbar,
propane: 35 – 50 mbar.
Setting of the gas pressure switch p
W
:
natural gas: 10 mbar,
propane: 30 mbar.
Gas connection: R ¾" external thread.
Material:
casing: stainless steel 430,
burner chamber: stainless steel 430,
BCU: PPE.
Ambient temperature:
-10 to +60°C. No condensation permitted.
Cycle lock: 15 s.
Capacity: 120 kW.
Gas consumption:
natural gas L: ± 11.7 m
3
/h,
natural gas H: ± 9.9 m
3
/h,
propane: ± 8.6 kg/h.
Connection rating:
230 V AC, -15/+10%, 50/60 Hz, 735 W.
Power consumption: I
A
/I
N
: ± 8 A/3.2 A.
Air circulation:
Controlled air flow: ± 6650 m
3
/h,
Heating: ± 8000 m
3
/h.
Jet length: 50 m.
Housing:
length: 1450 mm,
width (total): 650 m,
height/diameter: 532 mm,
weight: 45 kg.
Declaration of conformity
We, the manufacturer, hereby declare that the prod-
uct GP complies with the requirements of the listed
Directives and Standards.
Directives:
– 2009/142/EC
– 2004/108/EC
– 2006/42/EC
– 2006/95/EC
Standards:
– DIN 3362, EN 298
– EN 60730
– EN 1643, EN 525:2009
The relevant product corresponds to the type tested
by the notified body 0085.
The production is subject to the surveillance proce-
dure pursuant to Directive 2009/142/EC according
to annex II paragraph 3.
Elster-Instromet B.V.
Scan of the Declaration of conformity (D, GB) – see
www.docuthek.com