LED 5 flashes.
OFF
AUTO
+AUTO
1
2
3
4
5
!
Signal from safety temperature limiter (STL).
Temperature has been exceeded.
•
No fan run-on due to soiling. Clean, see page 12
!
Fan defective.
•
Check function of fan.
?
LEDs 4 and 5 flash.*
OFF
AUTO
+AUTO
1
2
3
4
5
!
Signal from safety temperature monitor (STM).
Temperature has been exceeded.
•
Leave heater to cool down for longer.
•
No fan run-on due to soiling. Clean, see page 12
?
LEDs and 5 flash.*
OFF
AUTO
+AUTO
1
2
3
4
5
!
During three consecutive restarts, the gas pres-
sure switch has tripped during the safety time
or flame proving period (gas pressure switch
oscillates).
•
Inlet pressure fluctuates. Establish stable gas
supply.
•
Gas pressure p
G
too low. Readjust gas pres-
sure p
G
, see page 6 (Adjusting the heater).
?
LEDs and 5 flash.
OFF
AUTO
+AUTO
1
2
3
4
5
!
Incorrect flame signal through conductive ce-
ramic insulation, e.g. surge via PE wire, possible.
•
Remedy incorrect flame signal. Replace ionization
electrode and, if necessary, the BCU as well.
?
LEDs and 5 flash.*
OFF
AUTO
+AUTO
1
2
3
4
5
!
Temperature sensor is not functioning correctly.
•
Check the temperature sensor connection.
•
Temperature sensor is below -20°C.
!
Temperature sensor defective.
•
Replace the temperature sensor.
?
LEDs and 4 flash.*
OFF
AUTO
+AUTO
1
2
3
4
5
!
The time (cycle lock) between two starts is too
short.
•
The BCU ensures there is a pause of 15 s be-
tween the starts. This warning is displayed during
this time.
?
LEDs and 4 flash.*
OFF
AUTO
+AUTO
1
2
3
4
5
!
The flame has gone out during operation. If a
restart has been programmed, an automatic re-
start is carried out provided that the burner has
been in operation for at least 2 s beforehand.
•
Poor flame signal due to incorrect burner ad-
justment. Readjust gas pressure p
G
•
Poor flame signal due to dirty or badly connected
ionization electrode. Clean the ionization elec-
trode and check for correct distance, see page 12
(Maintenance).
•
Check the cable connection for damage or mois-
ture. The plug must be fitted correctly.
•
Check the yellow and green burner ground cable
for corrosion and to ensure it is firmly connected.