2 Setup and Communications
2-8
F-PRO 5100 User Manual
D02416R04.00
Accessing the Relay’s SCADA Services
The relay supports DNP3 (Level 2) and Modbus SCADA protocols as a stan-
dard feature on all relays. DNP3 is available through a direct serial link or the
Ethernet LAN on top of either TCP or UDP protocols. The Modbus implemen-
tation supports both RTU (binary) or ASCII modes and is available through a
direct serial link.
The relay’s Port 3 is dedicated for use with Modbus or DNP3 serial protocols.
Port 3 uses standard RS-232 signalling. An external RS-232<->RS-485 con-
verter can also be used to connect to an RS-485 network.
For details on connecting to serial Port 3 see “Communicating with the Relay
(IED)” on page 2-2 and “Communication Port Details” on page 2-9.
The DNP3 protocol can also be run across the optional Ethernet LAN. Both
DNP over TCP and DNP over UDP are supported. For details on connecting
to the Ethernet LAN see “Network Link” on page 2-4.
Complete details on the Modbus and DNP3 protocol services can be found in
the Appendices, “Modbus RTU Communication Protocol” in Appendix E and
“DNP3 Communication Protocol” in Appendix F respectively.
Protocol Selection
To select the desired SCADA protocol, login to the relay’s user interface and
access the
Utilities>Setup>SCADA
menu. Select the protocol and set the cor-
responding parameters.
The DNP3 LAN/WAN - TCP and UDP options are only available if the
unit has an optional Ethernet LAN port installed.
Communication
Parameters
Port 3’s communication parameters are set using the
Utilities>Setup>Ports
menu in relay’s user interface. Both the baud rate and the parity bit can be con-
figured. The number of data bits and stop bits are determined automatically by
the selected SCADA protocol. Modbus ASCII uses 7 data bits. Modbus RTU
and DNP Serial use 8 data bits. All protocols use 1 stop bit except in the case
where either Modbus protocol is used with no parity; this uses 2 stop bits, as
defined in the Modbus standard.
Diagnostics
Protocol monitor utilities are available to assist in resolving SCADA commu-
nication difficulties such as incompatible baud rate or addressing. The utilities
can be access through the Maintenance user interface, for details see “Mainte-
nance Menu” on page 2-12.
Содержание F-PRO 5100
Страница 1: ...F PRO Feeder Protection Relay Model 5100 User Manual Version 4 0 Rev 0...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 10: ......
Страница 28: ......
Страница 94: ......
Страница 98: ......
Страница 140: ......
Страница 146: ......
Страница 168: ......
Страница 172: ......
Страница 174: ......
Страница 176: ......
Страница 178: ......
Страница 190: ......