![ERL F-PRO 5100 Скачать руководство пользователя страница 157](http://html1.mh-extra.com/html/erl/f-pro-5100/f-pro-5100_user-manual_2423787157.webp)
D02416R04.00
F-PRO 5100 User Manual
Appendix F-1
Appendix F DNP3 Communication Protocol
Device Profile
Vendor Name: ERLPhase Corporation
Device Name: Relay Model #
Highest DNP Level Supported:
Device Function:
For Requests: 2
_ Master
For Responses: 2
x Slave
Maximum Data Link Frame Size (octets):
Maximum Application Fragme Size (octets):
Transmitted: 292
Transmitted: 2048
Received: 292
Received: 2048
Maximum Data Link Re-tries:
Maximum Application Layer Re-tries:
_ None
x None
x Fixed at 3
_ Configurable, range __ to __
_ Configurable, range __ to __
Requires Data Link Layer Confirmation:
Requires Application Layer Confirmation:
_ Never
_ Never
_ Always
_ Always (not recommended)
_ Sometimes
x When reporting Event Data (Slave)
x Configurable, either always or never
x When sending multi-fragment responses
(Slave)
_ Sometimes
_ Configurable
Timeouts (in seconds) while waiting for:
Data Link Confirm
__None
x Fixed at 2
__Variable
__Configurable
Complete Application Fragment
x None
__Fixed at 2
__Variable
__Configurable
Application Confirm
__None
x Fixed at 5
__Variable
__Configurable
Complete Application Response
x None
__Fixed at 2
__Variable
__Configurable
Others__________________________
Select to execute delay
__None
x Fixed at 10
__Variable
__Configurable
Sends/Executes Control Operations:
WRITE Binary Outputs
x Never
__Always
__Sometimes
__Configurable
SELECT/OPERATE
__Never
x Always
__Sometimes
__Configurable
DIRECT OPERATE
__Never
x Always
__Sometimes
__Configurable
DIRECT OPERATE No ACK
__Never
x Always
__Sometimes
__Configurable
Count > 1
x Never
__Always
__Sometimes
__Configurable
Pulse On
__Never
x Always
__Sometimes
__Configurable
Pulse Off
x Never
__Always
__Sometimes
__Configurable
Latch On
__Never
x Always
__Sometimes
__Configurable
Latch Off
__Never
x Always
__Sometimes
__Configurable
Queue
x Never
__Always
__Sometimes
__Configurable
Clear Queue
x Never
__Always
__Sometimes
__Configurable
Maximum number of control objects per request: 16
Notes:
Control Trip/Close - Code Combination supported:
Latch On/NUL
Latch Off/NUL
Pulse On/NUL (Pulse duration fixed at 1 s)
Report Binary Input Change Events when no spe-
cific variation requested:
Reports time-tagged Binary Input Change
Events when no specific variation requested
__Never
__Never
__Only time-tagged
x Binary Input Change with Time
x Only non-time-tagged
_ Binary Input Change with Relative Time
_ Configurable to send both, one or the other
_ Configurable
Sends Unsolicited Response:
Sends Static Data in Unsolicited Responses:
x Never
x Never
_ Configurable
_ When Device Restarts
_Only certain objects
_ When Status Flags Change
_ Sometimes
No other options are permitted.
_ ENABLE/DISABLE UNSOLICITED Function
codes supported
Default Counter Object/Variation:
Counters Roll Over at:
x No Counter Reported
x No Counters Reported
_ Configurable
_ Configurable
Содержание F-PRO 5100
Страница 1: ...F PRO Feeder Protection Relay Model 5100 User Manual Version 4 0 Rev 0...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 10: ......
Страница 28: ......
Страница 94: ......
Страница 98: ......
Страница 140: ......
Страница 146: ......
Страница 168: ......
Страница 172: ......
Страница 174: ......
Страница 176: ......
Страница 178: ......
Страница 190: ......