Appendix B-8
F-PRO 5100 User Manual
D02416R04.00
Pickup Delay
1.00
seconds
0.00 to 99.99
59-2
Enabled
Gate Switch
OR
Pickup
70.0
volts
1.0 to 138.0
Pickup Delay
1.00
seconds
0.00 to 99.99
27 - Undervoltage
27-1
Enabled
Gate Switch
OR
Pickup
20.0
volts
1.0 to 120.0
Pickup Delay
1.00
seconds
0.00 to 99.99
27-2
Enabled
Gate Switch
OR
Pickup
20.0
volts
1.0 to 120.0
Pickup Delay
1.00
seconds
0.00 to 99.99
60 - Loss of Potential Alarm
60
Enabled
81 - Over/Under Frequency
81-1
Disabled
Pickup
60.005
Hz
[50.000,
59.995] or
[60.005,
70.000]
Pickup Delay
2.00
seconds
0.05 to 99.99
81-2
Disabled
Pickup
60.005
Hz
[50.000,
59.995] or
[60.005,
70.000]
Pickup Delay
2.00
seconds
0.05 to 99.99
81-3
Disabled
Pickup
59.995
Hz
[50.000,
59.995] or
[60.005,
70.000]
Pickup Delay
2.00
seconds
0.05 to 99.99
81-4
Disabled
Pickup
59.995
Hz
[50.000,
59.995] or
[60.005,
70.000]
Pickup Delay
2.00
seconds
0.05 to 99.99
32 - Directional Power
32P
Enabled
Pickup
3.00
amperes
[-15.00, -0.25]
or [0.25, 15.00]
F-PRO Settings Summary - Setting Group 1 [Setting Group 1]
Name
Symbol/Value
Unit
Range
Содержание F-PRO 5100
Страница 1: ...F PRO Feeder Protection Relay Model 5100 User Manual Version 4 0 Rev 0...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 10: ......
Страница 28: ......
Страница 94: ......
Страница 98: ......
Страница 140: ......
Страница 146: ......
Страница 168: ......
Страница 172: ......
Страница 174: ......
Страница 176: ......
Страница 178: ......
Страница 190: ......