4 Protection Functions
4-24
B-PRO User Manual 8700
D01908R02.12
Event Log
The relay maintains a log of events in a 250 entry circular log. Each entry con-
tains the time of the event plus an event description.
Logged events include trips, alarms, external input assertions plus internal
events such as setting changes. Phase information is included in event messag-
es where appropriate. For example, the event log entry for a device trip might
be:
2000 Nov 21, 15:34:19.832: 51 on ABC Trip
The event log can be viewed in three ways:
Front Panel
The front panel display shows events in abbreviated form
(Trip and Alarm events only).
Terminal User Interface
The full event log is available through the Event Log menu of
the terminal user interface.
SCADA
The protocols included in the B-PRO allow all the SCADA
master access to the event data from the relay (Trip and
Alarm events only).
www
. ElectricalPartManuals
. com
Содержание 8700/BUS
Страница 2: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 4: ...Preface ii B PRO User Manual 8700 D01908R02 12 w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 8: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 10: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 18: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 86: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 90: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 146: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 150: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 158: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 162: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 166: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...