Unit Description, BFU-21 and BFU-22
•
Battery Disconnect - on/off
•
DC out - on/off
18.4
Technical Data
18.4.1
Input Data
Table 135
Input data
Nominal input voltage
+24 V DC negative ground
Permitted variation input voltage
+18.0 to +29.0 V DC
Non-destruction input voltage
0.0 to +32.0 V DC
Power
4800 W
Nominal input current
200 A
Maximum input current
220 A
Maximum current ripple
(20 Hz - 20 kHz)
48 A
p-p
18.4.2
Output Data
Table 136
Output currents, BFU-21
RBS DC distribution (nominal)
160 A
RBS DC distribution (maximum)
180 A (during 3 hrs)
TM1 supply
12 A
TM2 supply
12 A
EC supply
1.5 A
Table 137
Output currents, BFU-22
RBS DC distribution (nominal)
160 A
RBS DC distribution (maximum)
180 A (during 3 hrs)
TM supply
40 A
18.4.3
Dimensions and Weight
Table 138
Dimensions and weight
Height
267 mm
Width
82 mm
Depth
226 mm
Weight
5 kg
EN/LZT 720 0008
P2A
2001-11-28
209 (485)
© Ericsson Radio Systems AB
— All Rights Reserved —