background image

IMPORTANT SAFETY INSTRUCTIONS

1.

SAVE THIS MANUAL - It contains important
safety and operating instructions for Power Supply
Models 19A704647 P1, P2, P3 and P11, P12, and
P14.

2.

Do not use auxiliary equipment not recommended or
sold by the manufacturer.  To do so may result in a
risk of fire, electric shock, or injury to personnel.

3.

Do not expose unit to rain, snow or other type of
moisture.

4.

To reduce risk of damage to electric plug and cord,
pull by plug rather than cord when disconnecting
unit.

5.

Make sure the cord is located so that it will not be
stepped on, tripped over, or otherwise subjected to
damage or stress.

6.

An extension cord should not be used unless abso-
lutely necessary.  Use of an improper extension cord
could result in a risk of fire and electric shock.  If an
extension cord must be used, make sure:

a.

That pins on plug of extension cord are the same
number, size and shapes of those on plug on unit.

b.

That extension cord is properly wired, in good
condition, and

c.

That wire size is large enough for AC ampere
rating of unit as specified in Table 1.

Table 1 - Recommended Minimum Size For

Extension Cords

Length of Extension Cord(ft.)

25

50

100

150

AWG Size of Extension Cord

18

18

16

14

7.

Do not operate unit with damaged cord or plug -
replace them immediately.

8.

Do not operate unit if it has received a sharp blow,
been dropped, or otherwise damaged in any way.
Return to a qualified service shop.

9.

Do not disassemble unit.  Return to a qualified serv-
ice shop when service or repair is required.  Incorrect
reassembly may result in a risk of electric shock or
fire.

10.

To reduce risk of electric shock, unplug unit from
outlet before attempting any maintenance or clean-
ing.

11.

GROUNDING  AND  AC  POWER  CORD
CONNECTION
 - To reduce risk of electrical shock
use only a properly grounded output.  The unit is
equipped with an electric cord having an equipment
grounding conductor and a grounding plug.  Be sure
that the outlet is properly installed and grounded in
accordance with all local codes and ordinances.

12.

DANGER - Never alter AC cord or plug.  If it does
not fit the outlet, have a proper outlet installed by a
qualified electrician.  Improper connection can result
in risk of electric shock.

13.

This unit is for use on a 121 volt circuit, and has a
grounding plug that looks like the plug shown in
Figure 1.  A temporary adapter, that looks like the
adapter shown in sketches B and C, may be used to
connect this plug to a two pole receptacle as shown
in sketch B if a properly grounded outlet is not
available. The temporary adapter should be used only
until a properly grounded outlet can be installed by a
qualified electrician.

14.

DANGER - Before using the adapter shown, be
certain that the center screw of the outlet plate is
grounded.  The green colored rigid ear or lug extend-
ing from the adapter must be connected to a properly
grounded outlet -- make certain it is grounded.  If
necessary, replace original outlet cover plate screw
with a longer screw that securely fastens the ear or
lug to outlet cover plate and makes a grounded con-
nection to outlet box.

Figure 1 - Grounding Methods

LBI-38751

4

Содержание 19A704647P1

Страница 1: ...SHOCK DO NOT USE THIS POLARIZED PLUG WITH AN EXTENSION CORD RECEPTACLE OR OTHER OUTLET UNLESS THE BLADES CAN BE FULLY INSERTED TO PREVENT BLADE EXPOSURE THESESERVICING INSTRUCTIONS ARE FOR USE BYQUAL...

Страница 2: ...orized service technician or facility designated by the supplier Any repairs alterations or substitution of recommended parts made by the user to this equipment notapproved by the manufacturer could v...

Страница 3: ...he use of the service technician Refer to the appropriate Specification Sheet for complete specifications 19A704647P1 P3 ULApproval 19A704647P11 P12 CSA UL Approval Pending 19A704647P14 European Appro...

Страница 4: ...fied serv ice shop when service or repair is required Incorrect reassembly may result in a risk of electric shock or fire 10 To reduce risk of electric shock unplug unit from outlet before attempting...

Страница 5: ...of Q1 Q2 R1 and R2 In order to control the output voltage of the supply the series pass tran sistors are operated as variable resistors If the load on the supply is increased causing a drop in the out...

Страница 6: ...his winding at J6 and J7 along with D2 and C9 into approximately 30 volts DC at nominal line voltage This bias voltage then provides power to all to the internal circuitry of the supply OPERATION 1 Co...

Страница 7: ...tion If trouble persists check with a qualified service person TROUBLESHOOTING TABLE SYMPTOM AREA TO CHECK FUSE BLOWS 1 shorted output 2 shorted D1 C1 C2 C3 T1 VR1 RV1 F1 NO OUTPUT 1 shorted output 2...

Страница 8: ...er using wirenut see Diagram for 240 Volt operation 6 Cover insulate exposed BRN WHT lead to prevent accidental contact 7 Move BLACK wire from J7 to J8 Power supply can now be used with a 240 Volt 50...

Страница 9: ...Figure 2 Power Supply Internal View Ericsson Inc Private Radio Systems Mountain View Road Lynchburg Virginia 24502 1 800 528 7711 Outside USA 804 528 7711 Printed in U S A LBI 38751 9...

Страница 10: ...1503 Nut 10 32 KEPS 15 M29 11003300 TY WRAP or M29 11024500 TY WRAP 16 M29 22039701 Wire Nut 17 M29 07063200 Case P2 P3 P12 SYMBOL PART NO DESCRIPTION 18 M29 07070400 Cover 19 M29 35002600 Rubber feet...

Страница 11: ...OUTLINE DIAGRAM HEATSINK ASSEMBLY P C BOARD 13 VOLT POWER SUPPLY EARLIER VERSION LBI 38751 11...

Страница 12: ...OUTLINE DIAGRAM PC BOARD LATER VERSION LBI 38751 12...

Страница 13: ...OUTLINE DIAGRAM 13 VOLT POWER SUPPLY 19A70647P1 P3 P11 P12 P14 LBI 38751 13...

Страница 14: ...SCHEMATIC DIAGRAM 13 VOLT POWER SUPPLY 19A70467P1 P2 P11 P12 LBI 38751 14...

Страница 15: ...SCHEMATIC DIAGRAM 13 VOLT POWER SUPPLY 19A704647P3 P14 LBI 38751 15...

Страница 16: ...ADAPTER CABLE 19B803437P1 LBI 38751 16...

Отзывы: