TROUBLESHOOTING

Fault codes 

The following is the fault code table of outdoor units. 

Table 1 Outdoor fault code 

Fault 

code 

Fault 

d

escription 

Possible 

r

eason

s for

 

a

bnormality 

How to 

d

eal 

w

ith 

R

emarks

 

Outdoor ambient 

temperature sensor 

fault 

1.The outdoor ambient temperature

sensor is connected loosely;

2.The outdoor ambient temperature

sensor fails to work;

3.The sampling circuit fails.

1.Reconnect the outdoor

ambient temperature sensor;

2.Replace the outdoor ambient

temperature sensor

components;

3.Replace the outdoor control

board components.

Outdoor coil 

temperature sensor 

fault 

1.The outdoor coil temperature

sensor is connected loosely;

2.The outdoor coil temperature

sensor fails to work;

3.The sampling circuit fails.

1.Reconnect the outdoor coil

temperature sensor;

2.Replace the outdoor coil

temperature sensor

components;

3.Replace the outdoor control

board components.

3  The unit over-current 

turn off fault 

1. Control board current sampling

circuit fails;

2. The current is over high because

the supply voltage is too low;

3. The compressor is blocked;

4. Overload in cooling mode;

5. Overload in heating mode.

1. Replace the electrical control

board components;

2. Normally protection

3. Replace the compressor

4. Please see the Note 3

5. Please see the Note 4

4  EEprom Data error 

1.EE components fails;

2.EE components control circuit

fails;

3.EE components are inserted

incorrectly.

1.Replace the EE components;

2.Replace the outdoor control

board components;

3.Reassembly the EE

components.

Cooling freezing 

protection (the indoor 

coil temperature is too 

low) or heating 

overload (indoor coil 

temperature is too 

high) 

1.The indoor unit can not blow air

normally;

2.The room temperature is too low in

cooling mode or the room

temperature is too high in heating;

3.The filter is dirty;

4.The duct resistance is too high to

result in low air flow;

5.The setting fan speed is too low;

6.The indoor unit is not  installed in

accordance with the installation

standards, and the air inlet is too

close to the air outlet .

1.Check whether the indoor fan,

indoor fan motor and

evaporator work normally;

2.Normal protection;

3.Clean the filter;

4.Check the volume control

valve, duct length etc.;

5.Set the speed with high speed;

6.Reinstall the indoor unit

referring to the user manual to

change the distance between

the indoor unit and the wall or

ceiling.

The communication 

fault between the 

indoor unit and 

outdoor unit 

1.

2.

The connection cable is connected 

improperly between the indoor unit 

and outdoor unit;

The communication cable is 

connected loosely;

3.The communication cable fails;

4.The indoor control board fails;

5.The outdoor control board fails;

6.Communication circuit fuse open;

7.The specification of

communication cable is incorrect.

1.

2.

3.

Reconnect the connection 

cable referring to the wiring 

diagram;

Reconnect the communication 

cable;

Replace the communication 

cable;

4.Replace the indoor control

board;

5.Replace the outdoor control

board;

6.Check the communication

circuit, adjust the DIP switch

and the short-circuit fuse.

7.Choose suitable

communication cable

referring to the user manual

Содержание EAC2H18R2C

Страница 1: ...r purchasing our air conditioner Please read this owen s manual carefully before using your air conditioner Model No EAC2H18R2C EAC4H36R2C EAC3H24R2C EAC5H42R2C Multi Zone Mini Split Air Conditioner T...

Страница 2: ...cy operation with portable convenience By following the operating and care instructions in this manual your air conditioner will provide you with many years of reliable service Please visit our websit...

Страница 3: ...t has been blocked Remove block obstacles Poor cooling heating 1 The outdoor heat exchanger is dirty such as condenser 2 3 There are heating devices indoors The air tightness is not enough People come...

Страница 4: ...ontrol board TO CHECK CODES 1 EAC2H18R2C 2 EAC2H18R2C EAC4H36R2C EAC3H24R2C EAC5H42R2C Drive failure indicator Main control failure indicator Main Control Board Main control failure Fault code will di...

Страница 5: ...4 TROUBLESHOOTING Drive fault code display s...

Страница 6: ...board components 3 Reassembly the EE components 5 Cooling freezing protection the indoor coil temperature is too low or heating overload indoor coil temperature is too high 1 The indoor unit can not...

Страница 7: ...8 AC voltage is abnormal 1 The AC voltage 275V or 160V 2 The AC voltage of sampling circuit on the driver board is abnormal 1 Normal protection please check the supply power 2 Replace the driver board...

Страница 8: ...LESHOOTING You can check the driver board LED to further a ze the fault code of the drive board and to learn about what leads to the fault and how to operate it information can be n in d r s for a d w...

Страница 9: ...SHOOTING d r s for a d w emarks 1 is ed ly 2 s 3 s 4 s Too high d that the is longer 3 fails 4 1 2 ring 1 connecting is 2 per fails 3 per fails 4 per s 5 per per Lacking of ring 1 connecting is 2 s 3...

Страница 10: ...connected loosely 2 The sequence of the wiring between the wired controller to the indoor control board is wrong 3 The wiring between the wired controller to the indoor control board fails 4 The wire...

Страница 11: ...as condenser 5 The speed of the outdoor fan motor is too low Check the outdoor fan motor and fan capacitor 6 The outdoor fan is broken or the outdoor fan is blocked Check the outdoor fan 7 The air in...

Страница 12: ...hange the driver board 14 PFC LOW voltage detected failure 15 AD offset abnormal detected failure Driver board fails Change the driver board 16 Inverter PWM logic set fault 17 Inverter PWM initializat...

Страница 13: ...ty How to deal with failure in drive control 1 C is not ed properly 2 3 4 5 6 fails 1 2 3 the is d 4 5 6 2 failure in drive control 1 2 3 2 3 3 4 failure in drive control 1 2 3 ils 1 2 ils 3 4 2 3 2 3...

Страница 14: ...d 18 Driver board read EE data error 1 EEPROM has no data or data error 2 EEPROM circuit fault 1 Change EEPROM component 2 Change the driver board 19 PFC chip receive data fault Abnormal communication...

Страница 15: ...Emerson Quiet Kool Co Ltd 120 US 46 Parsippany Troy Hills NJ 07054 Toll Free 1 888 493 0305 Version Update 2021 5 0...

Отзывы: