TROUBLESHOOTING

NOTE 1

If the indoor unit can not start or the indoor unit stops itself after 30s, at the same time the unit do 
not display the fault code, please check the fire and the socket of the control board. 

NOTE 2

If the indoor unit displays the 75,76,77,78 fault code after you turn on the unit, please check the 
TEST seat of the indoor control board or the TEST detection circuit to see whether short circuit 
occurs. 

NOTE 3

: Overload in cooling mode  

Overload in cooling mode 

sr. 

The root cause 

Corrective measure 

The refrigerant is excessive. 

Discharge the refrigerant, and recharge 
the refrigerant referring to the rating label.  

The outdoor ambient temperature is too high. 

Please use within allowable temperature range 

Short-circuit occurs in the air outlet and air inlet of 
the outdoor unit.

Adjust  the  installation  of the  outdoor  unit 
referring  to the user manual.  

The  outdoor  heat  exchanger  is  dirty,  such 
as condenser.  

Clean the heat exchanger of the outdoor unit, 
such as condenser.  

The speed of the outdoor fan motor is too low. 

Check the outdoor fan motor and fan capacitor. 

The  outdoor  fan  is  broken  or  the  outdoor  fan 
is blocked.  

Check the outdoor fan. 

The air inlet and outlet has been blocked. 

Remove the blocked objects. 

The expansion valve or the capillary fails. 

Replace the expansion valve or the capillary. 

NOTE 4

: Over load in heating mode 

Overload in heating mode 

sr. 

The root cause 

Corrective measure 

The refrigerant is excessive. 

Discharge the refrigerant, and recharge 
the refrigerant referring to the rating label.  

The indoor ambient temperature is too high. 

Please use within allowable temperature range. 

Short-circuit   occurs in the air outlet and air 
inlet of the indoor unit.

Adjust the installation of the indoor unit referring 
to the user manual.  

The indoor filter is dirty. 

Clean the indoor filter. 

The speed of the indoor fan motor is too low. 

Check the indoor fan motor and fan capacitor. 

The indoor fan is broken or the outdoor fan 
is blocked.  

Check the indoor fan. 

The air inlet and outlet has been blocked. 

Remove the blocked objects. 

The expansion valve or the capillary fails.

Replace the expansion valve or the capillary. 

Содержание EAC2H18R2C

Страница 1: ...r purchasing our air conditioner Please read this owen s manual carefully before using your air conditioner Model No EAC2H18R2C EAC4H36R2C EAC3H24R2C EAC5H42R2C Multi Zone Mini Split Air Conditioner T...

Страница 2: ...cy operation with portable convenience By following the operating and care instructions in this manual your air conditioner will provide you with many years of reliable service Please visit our websit...

Страница 3: ...t has been blocked Remove block obstacles Poor cooling heating 1 The outdoor heat exchanger is dirty such as condenser 2 3 There are heating devices indoors The air tightness is not enough People come...

Страница 4: ...ontrol board TO CHECK CODES 1 EAC2H18R2C 2 EAC2H18R2C EAC4H36R2C EAC3H24R2C EAC5H42R2C Drive failure indicator Main control failure indicator Main Control Board Main control failure Fault code will di...

Страница 5: ...4 TROUBLESHOOTING Drive fault code display s...

Страница 6: ...board components 3 Reassembly the EE components 5 Cooling freezing protection the indoor coil temperature is too low or heating overload indoor coil temperature is too high 1 The indoor unit can not...

Страница 7: ...8 AC voltage is abnormal 1 The AC voltage 275V or 160V 2 The AC voltage of sampling circuit on the driver board is abnormal 1 Normal protection please check the supply power 2 Replace the driver board...

Страница 8: ...LESHOOTING You can check the driver board LED to further a ze the fault code of the drive board and to learn about what leads to the fault and how to operate it information can be n in d r s for a d w...

Страница 9: ...SHOOTING d r s for a d w emarks 1 is ed ly 2 s 3 s 4 s Too high d that the is longer 3 fails 4 1 2 ring 1 connecting is 2 per fails 3 per fails 4 per s 5 per per Lacking of ring 1 connecting is 2 s 3...

Страница 10: ...connected loosely 2 The sequence of the wiring between the wired controller to the indoor control board is wrong 3 The wiring between the wired controller to the indoor control board fails 4 The wire...

Страница 11: ...as condenser 5 The speed of the outdoor fan motor is too low Check the outdoor fan motor and fan capacitor 6 The outdoor fan is broken or the outdoor fan is blocked Check the outdoor fan 7 The air in...

Страница 12: ...hange the driver board 14 PFC LOW voltage detected failure 15 AD offset abnormal detected failure Driver board fails Change the driver board 16 Inverter PWM logic set fault 17 Inverter PWM initializat...

Страница 13: ...ty How to deal with failure in drive control 1 C is not ed properly 2 3 4 5 6 fails 1 2 3 the is d 4 5 6 2 failure in drive control 1 2 3 2 3 3 4 failure in drive control 1 2 3 ils 1 2 ils 3 4 2 3 2 3...

Страница 14: ...d 18 Driver board read EE data error 1 EEPROM has no data or data error 2 EEPROM circuit fault 1 Change EEPROM component 2 Change the driver board 19 PFC chip receive data fault Abnormal communication...

Страница 15: ...Emerson Quiet Kool Co Ltd 120 US 46 Parsippany Troy Hills NJ 07054 Toll Free 1 888 493 0305 Version Update 2021 5 0...

Отзывы: