41
Operating Guide
PSI 8000 2U Series
EN
Date: 28-06-2012
About the power supply
2.2 Model specific data
* Related to the nominal value, the accuracy defines the maximum allowed deviation between set value and actual value.
Example: a 80V model has min. 0.2% voltage accuracy. This is 160mV. When setting a voltage of 5V and with an allowed maximum deviation of 160mV, the resulting
actual value could be between 4.84V and 5.16V.
** Optional, unlockable feature
PSI 8032-20 2U PSI 8065-10 2U PSI 8160-04 2U PSI 8080-40 2U PSI 8040-60 2U PSI 8080-60 2U
Mains input
Input voltage
90…264V
90…264V
90…264V
90…264V
90…264V
90…264V
- with derating
-
-
-
-
90...150V
90...150V
Input current at 230V
max. 3.2A
max. 3.4A
max. 3.2A
max. 4.8A
max. 7.5A
max. 7.5A
Input frequency
45…65Hz
45…65Hz
45…65Hz
45…65Hz
45…65Hz
45…65Hz
Input fuse
T 8A
T 8A
T 8A
T 16A
T 16A
T 16A
Power factor
> 0.99
> 0.99
> 0.99
> 0.99
> 0.99
> 0.99
Output - Voltage
Nominal voltage U
Nom
32V
65V
160V
80V
40V
80V
Adjustable range
0V…U
Nom
0V…U
Nom
0V…U
Nom
0V…U
Nom
0V…U
Nom
0V…U
Nom
Stability at mains fluctuation ±10%
∆
U
IN
< 0.02%
< 0.02%
< 0.02%
< 0.02%
< 0.02%
< 0.02%
Stability at 10…90% load
< 0.05%
< 0.05%
< 0.05%
< 0.05%
< 0.05%
< 0.05%
Ripple P-P
< 100mV
< 150mV
< 120mV
< 10mV
< 10mV
< 10mV
Ripple RMS
< 8mV
< 10mV
< 20mV
< 4mV
< 4mV
< 4mV
Accuracy *
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
Resolution of display
10mV
10mV
100mV
10mV
10mV
10mV
Remote sense compensation
max. 2.0V
max. 2.0V
max. 2.0V
max. 2.0V
max. 2.0V
max. 2.0V
Overvoltage protection (adjustable)
0…35.2V
0…71.5V
0…176V
0…88V
0…44V
0…88V
Output - Current
Nominal current I
Nom
20A
10A
4A
40A
60A
60A
Adjustable range
0…I
Nom
0…I
Nom
0…I
Nom
0…I
Nom
0…I
Nom
0…I
Nom
Stability at mains fluctuation ±10%
∆
U
IN
< 0.05%
< 0.05%
< 0.05%
< 0.05%
< 0.05%
< 0.05%
Stability at 0…100%
∆
U
OUT
< 0.15%
< 0.15%
< 0.15%
< 0.15%
< 0.15%
< 0.15%
Ripple P-P
< 65mA
< 25mA
< 3mA
< 19mA
< 100mA
< 100mA
Ripple RMS
< 10mA
< 3mA
< 1mA
< 7mA
< 7mA
< 7mA
Accuracy *
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
Resolution of display
10mA
10mA
1mA
10mA
10mA
10mA
Transient recovery time 10….90% load
< 2ms
< 2ms
< 2ms
< 2ms
< 2ms
< 2ms
Output - Power
Nominal power P
Nom
640W
650W
640W
1000W
1500W
1500W
Nominal power at derating
-
-
-
-
1000W
1000W
Adjustable range
-
-
-
0...P
Nom
0...P
Nom
0...P
Nom
Accuracy *
-
-
-
≤
1%
≤
1%
≤
1%
Resolution of display
0.1W
0.1W
0.1W
1W
1W
1W
Output - Internal resistance **
Max. adjustable resistance
32.00
Ω
130.0
Ω
800.0
Ω
40.00
Ω
13.33
Ω
26.67
Ω
Accuracy *
< 2%
< 2%
< 2%
< 2%
< 2%
< 2%
Resolution of display
10m
Ω
100m
Ω
100m
Ω
10m
Ω
10m
Ω
10m
Ω
Regulation time of set value to actual val.
~ 2s
~ 2s
~ 2s
~ 2s
~ 2s
~ 2s
Miscellaneous
Efficiency
90.5%
93.0%
93.0%
90.5%
90.5%
90.5%
Ambient temperature
0…50°C
0…50°C
0…50°C
0…50°C
0…50°C
0…50°C
Storage temperature
-20…70°C
-20…70°C
-20…70°C
-20…70°C
-20…70°C
-20…70°C
Humidity rel.
< 80%
< 80%
< 80%
< 80%
< 80%
< 80%
Dimensions (WxHxD) standard model
19" 2U 380mm
19" 2U 380mm
19" 2U 380mm
19" 2U 460mm
19" 2U 460mm
19" 2U 460mm
Dimensions (WxHxD) option ZH
19" 2U 380mm
19" 2U 380mm
19" 2U 380mm
19" 2U 460mm
19" 2U 460mm
19" 2U 460mm
Weight standard model
9.5kg
9.5kg
9.5kg
13.5kg
13.5kg
13.5kg
Weight with option ZH
11kg
11kg
11kg
15kg
15kg
15kg
Isooutput to enclosure
500V DC
500V DC
500V DC
500V DC
500V DC
500V DC
Isolation -output to enclosure
Isolation input to output
Cooling
Safety
EMC standards
Overvoltage class
Protection class
Pollution degree
Operational altitude
Series operation
Master-Slave
Parallel operation
Master-Slave
Analogue programming
Input range
Accuracy
Input impedance
Article number
09230417
09230418
09230419
09230410
09230425
09230411
no
2500V DC
by fans, air inlet on the front, air exhaust on the rear
EN 60950
EN 61326, EN 55022 Class B
1
2
<2000m
possible (with restrictions)
53kOhm
yes, with current distribution via Share bus
yes, via analog interface
300V DC
0…5V or 0…10V, selectable
≤
0.2%
2