IP350-Plus,

   

IP500-Plus 

IP1000-Plus, IP1500-Plus 

IP2000-Plus, IP3000-Plus 

IP4000-Plus, IP5000-Plus 

 

 

 

 

Pure sine wave inverter 

 

USER MANUAL 

Содержание IP1000-11-Plus

Страница 1: ...IP350 Plus IP500 Plus IP1000 Plus IP1500 Plus IP2000 Plus IP3000 Plus IP4000 Plus IP5000 Plus Pure sine wave inverter USER MANUAL...

Страница 2: ......

Страница 3: ...LCD interface 18 5 3 1 Real time interface 18 5 3 2 Parameters setting 18 5 3 3 Power Saving Mode 18 5 3 4 Parameters user define 20 5 4 Error code 21 6 Installation 22 6 1 Attentions 22 6 2 Wire siz...

Страница 4: ......

Страница 5: ...the device damaged WARNING Indicates the danger of electric shock if not avoided would cause casualties WARNING HOT SURFACE Indicates the risk of high temperature if not avoided would cause scalds Re...

Страница 6: ...ected to the ground The cross section of the wire should not be less than 4mm2 The DC input voltage must strictly be following the parameter table Too high or too low DC input voltage will affect the...

Страница 7: ...nal conductive modules could be touched The inverter is allowed to restart after removing the faults which affects safety performance There are no serviceable parts inside If any maintenance service i...

Страница 8: ...so suitable for occasions with high power quality requirements Features Completely electrically isolated design for input and output Full digital double closed loop control Excellent EMC characteristi...

Страница 9: ...er for the IP350 Plus series Configure the parameters via the local LCD meter no including the IP350 Plus series remote LCD meter phone Apps or PC software This function is unavailable for inverters w...

Страница 10: ...T terminal C Chinese dual socket N North America Appearance without decorative cover is suitable for AC output of A Australia E European F French UK United Kingdom IP500 xx Plus Appearance with decor...

Страница 11: ...7 Appearance without decorative cover is suitable for AC output of A Australia E European F French UK United Kingdom IP1000 xx Plus IP1500 xx IP2000 2x IP2000 4x IP3000 42 Plus...

Страница 12: ...8 IP2000 1x Plus IP3000 1x Plus IP3000 2x Plus...

Страница 13: ...ions to start the cooling fan Heat sink temperature is higher than 45 or The internal inverter temperature is higher than 45 or The output power is higher than 50 of the rated power IP350 11 Plus IP35...

Страница 14: ...ure is lower than 40 and The output power is lower than 30 of the rated power IP350 11 Plus IP350 12 Plus IP350 21 Plus IP350 22 Plus IP500 11 Plus IP500 12 Plus IP500 21 Plus IP500 22 Plus Heat sink...

Страница 15: ...lus IP4000 41 Plus IP4000 42 Plus IP5000 42 Plus AC outlet types include A Australia C Chinese dual socket E European F French N North America GFCI Ground fault circuit interrupt UK United Kingdom and...

Страница 16: ...licable product Number T Terminal IP Plus series 1 pcs C Chinese dual socket IP350 500 x2 Plus 1 pcs IP1000 1500 2000 x2 Plus 2 pcs E European IP350 500 x2 Plus 1 pcs IP1000 1500 2000 3000 x2 Plus 2 p...

Страница 17: ...pcs IP2000 x1 Plus 2 pcs GFCI Ground Fault Circuit Interrupt IP1000 1500 2000 x1 Plus 1 pcs 1 pcs terminal 1 pcs outlet for the AC output port Type Appearance Applicable product Number TA Terminal Au...

Страница 18: ...g 1 If the red LED is ON solid it indicates that the GFCI outlet is damaged please replace a new one 2 If the LED is green ON after it flashes in red three times connect the circuit breaker and the ni...

Страница 19: ...ection diagram IP350 xx Plus take the Appearance with decorative cover as an example IP500 xx Plus take the Appearance with decorative cover as an example IP1000 xx IP1500 xx IP2000 2x IP2000 4x IP300...

Страница 20: ...0 4x Plus CAUTION It is recommended to connect the inverter DC input terminal to the battery terminal directly DO NOT connect it to the charge source terminal Otherwise the charging voltage spikes of...

Страница 21: ...ng interface press it for 2s to enter the parameters configuration interface Click Move down parameter decrease Press for 2s Press it to turn on off the load output default ON in the real time interfa...

Страница 22: ...ameter Step4 Click or to configure the parameter value Step5 Press for 2s to confirm the configuration Step6 Click to exit the current interface 5 3 3 Power Saving Mode Users can enable the power savi...

Страница 23: ...saving mode PSO Step1 In the parameters setting interface click the or button to select the PSO parameter Step2 Press and hold the button until the PSO value flashes Step3 Click the or button to set t...

Страница 24: ...User define Output voltage class 220VAC 220VAC 230VAC 240VAC 110VAC 100VAC 110VAC 120VAC Output frequency class 50Hz 50Hz 60Hz LCD backlight time 30s 30s 60s 100s ON solid Power Saving Enable OFF ON...

Страница 25: ...ayed on the LCD is 1152 For the parameter user defines please refer to the input voltage rules in Chapter 7 Protections Otherwise the parameter setting will not succeed 5 4 Error code Error code Fault...

Страница 26: ...cables according to the current density of 3 5A mm2 or less Avoid direct sunlight and rain infiltration when installing it outdoor After turn off the power switch do not open or touch the internal com...

Страница 27: ...16mm2 5AWG RNB14 6S DC 2P 63A IP3000 11 Plus 25mm2 3AWG 4 RNB80 10 DC 125A 3P in parallel IP3000 12 Plus 25mm2 3AWG 4 RNB80 10 DC 125A 3P in parallel IP3000 21 Plus 25mm2 3AWG 2 RNB60 6 DC 100A 2P in...

Страница 28: ...WG AC 2P 16A IP2000 41 Plus 4mm2 11AWG AC 2P 32A IP2000 42 Plus 2 5mm 13AWG AC 2P 16A IP3000 11 Plus 6mm2 10AWG AC 2P 50A IP3000 12 Plus 4mm2 11AWG AC 2P 25A IP3000 21 Plus 6mm2 10AWG AC 2P 50A IP3000...

Страница 29: ...ld install the inverter in a place with sufficient airflow and a minimum clearance of 150mm from the inverter s upper and lower edges CAUTION Ventilation is highly recommended if mounted in an enclosu...

Страница 30: ...ore wiring During wiring do not connect the circuit breaker or fuse Ensure the poles leads are polarity correctly A fuse whose current is 2 to 2 5 times the inverter s rated current must be installed...

Страница 31: ...a wire diameter of not more than 4mm2 Add solder to the connection point when selecting the multi stranded wire and directly insert it into the corresponding port Stop the inverter before removing the...

Страница 32: ...the AC load Optional accessories 1 RS485 communication port RJ45 Pin Definition Pin Definition Pin Definition 1 5VDC 5 RS 485 A 2 5VDC 6 RS 485 A 3 RS 485 B 7 GND 4 RS 485 B 8 GND 2 Connect optional...

Страница 33: ...Turn on the AC loads one by one and check the inverter s running status and the loads CAUTION When supplying power for different loads turning on the load with a large impulse current is recommended A...

Страница 34: ...30 6 4 Rotate the LCD Remove the screws of the LCD unit with a screwdriver and rotate it 180 Secure the screws of the LCD unit to the inverter...

Страница 35: ...Low voltage disconnect voltage 1V D Low voltage disconnect voltage Low voltage limiting voltage 10 5 21 42V Detail status is shown as the following when the input voltage protection occurs Input volt...

Страница 36: ...Rated power The output is switched OFF after 30 seconds Buzzer beeps The red indicator slowly flashes LCD displays the S 1 8Pe S Output power Pe Rated power The output is switched OFF after 10 seconds...

Страница 37: ...ps The red indicator slowly flashes LCD displays the S 1 7Pe S Output power Pe Rated power The output is switched OFF after 5 seconds Buzzer beeps The red indicator slowly flashes LCD displays the IP5...

Страница 38: ...CD displays the Note The AC output is recovered automatically three times recover after 5s 10s 15s separately After the recovery attempt failed three times you need to restart the inverter to recover...

Страница 39: ...heck whether the DC input voltage is higher than16 32 64V by a multimeter The inverter will resume work after adjusting the input voltage Red indicator slowly flashes Buzzer beeps Overload Reduce the...

Страница 40: ...or LCD is consistent with the actual operation Pay attention to any troubleshooting or error indications Take corrective action if necessary Check all the terminals for signs of corrosion insulation d...

Страница 41: ...urrent when power on 30A 50A Output voltage 100VAC 110VAC 3 120VAC 7 3 Output frequency 50 60Hz 0 2 Output wave Pure Sine Wave Output distortion THD THD 4 Resistive load THD 3 Resistive load THD 4 Res...

Страница 42: ...ltage 100VAC 110VAC 3 120VAC 7 3 Output frequency 50 60Hz 0 2 Output wave Pure Sine Wave Output distortion THD THD 4 Resistive load THD 3 Resistive load THD 4 Resistive load Load power factor 0 2 1 Lo...

Страница 43: ...distortion THD THD 5 Resistive load THD 4 Resistive load THD 4 Resistive load Load power factor 0 2 1 Load power Continuous output power Rated input voltage 12VDC 24VDC 48VDC Input voltage range 10 8...

Страница 44: ...4 Resistive load THD 4 Resistive load Load power factor 0 2 1 Load power Continuous output power Rated input voltage 12VDC 24VDC 48VDC 48VDC Input voltage range 10 8 16 0VDC 21 6 32 0VDC 43 2 64 0VDC...

Страница 45: ...t power Rated input voltage 12VDC 24VDC 12VDC 24VDC Input voltage range 10 8 16 0VDC 21 6 32VDC 10 8 16 0VDC 21 6 32VDC Rated output efficiency 89 0 90 0 89 5 91 5 Max output efficiency 90 0 70 loads...

Страница 46: ...power Continuous output power Rated input voltage 12VDC 24VDC 12VDC 24VDC 48VDC Input voltage range 10 8 16 0VDC 21 6 32 0VDC 10 8 16 0VDC 21 6 32 0VDC 43 2 64 0VDC Rated output efficiency 89 0 90 0 8...

Страница 47: ...Continuous output power Rated input voltage 12VDC 24VDC 48VDC Input voltage range 10 8 16 0VDC 21 6 32 0VDC 43 2 64 0VDC Rated output efficiency 88 0 90 0 92 5 Max output efficiency 94 0 30 loads 93...

Страница 48: ...d input voltage 12VDC 24VDC 48VDC 48VDC 48VDC Input voltage range 10 8 16 0VDC 21 6 32 0VDC 43 2 64 0VDC 43 2 64VDC 43 2 64 0VDC Rated output efficiency 87 0 90 0 92 5 91 0 91 0 Max output efficiency...

Страница 49: ...idity 95 N C Enclosure IP20 Altitude 5000m If the altitude exceeds 1000 meters the rated power will be reduced according to IEC62040 Certification Category Standard No Safety EN IEC62109 1 UL1741 UL45...

Страница 50: ...alue of the inverter Damage caused by working temperature exceeds the rated range Arc fire explosion and other accidents are caused by failure to follow the inverter stickers or manual instructions Di...

Страница 51: ......

Страница 52: ...HUIZHOU EPEVER TECHNOLOGY CO LTD Beijing Tel 86 10 82894896 82894112 Huizhou Tel 86 752 3889706 E mail info epever com Website www epever com...