14
TE - Te
European
IP4000/5000-42-Plus
Terminal*1
Outlet*1
TF - Te
French
TN - Te
America
IP3000-x1-Plus
IP4000-41-Plus
Terminal*1
Outlet*1
GFCI outlets need to be tested after power-on to ensure proper operation.
Preparation
Connect a circuit breaker and an AC load (it is recommended to use a night light to observe the status
conveniently) to the GFCI outlet. Turn on the inverter after confirming the wiring.
Testing
1) If the red LED is ON solid, it indicates that the GFCI outlet is damaged; please replace a new one.
2) If the LED is green ON after it flashes in red three times, connect the circuit breaker, and the night light
will be turned on. Then, press the "TEST" button to observe the testing status:
①
The "TEST" button always pops up, and the night light keeps ON solid. It indicates that the GFCI
wiring is an error; please correct the wrong wiring.
②
The "TEST" button goes down, while the "RESET" button pops up. The LED and the night light are
turned off, indicating the GFCI outlet is normal (
Note: Press the "RESET" button again to
recover the load output)
.