- 12 -
The inverter needs to be lifted up and then slid down over the hooks making sure that
the connecting points in the bracket and in the back of the inverter engage properly.
5
Electrical Connection
5.1 General safety instruction
DANGER!
Improper operation during the wiring process can cause fatal injury to
operator or unrecoverable damage to the inverter.
Only qualified personnel can perform the wiring work.
DANGER!
Before you connect the inverter, disconnect the AC and DC sides from all
power sources and secure them against being inadvertently switched back on.
WARNING!
Always respect the nominal ratings of voltage and current specified in section
4 (Technical Data) when designing your system. Please observe these
considerations when designing the photovoltaic field:
Maximum DC voltage input to each MPPT circuit: 520 V
Maximum DC current input to each MPPT circuit:
20A for
(3,*.
WARNING!
Check the national and local standard regulations to make sure that your
electrical installation design is in compliance with them.
NOTICE
All cables must be firmly attached, undamaged, properly insulated and
adequately dimensioned.