Special Instructions

During operation of the sauna, very high temperatures

are created within the cabin and particularly at the sto-

ve. If the stove is not installed correctly there will be a

fire hazard. Please read these installation instructions

carefully. You should pay particular attention to the

specified measurements and to the instructions below.

l

The sauna heating unit is designed for operation with

an input voltage of 400 V AC 3N through the sauna

control unit.

l

Installation  and  electrical  connection  of  the  sauna

heating  units,  the  control  unit  and  other  electrical

components  must  be  performed  by  a  qualified

electrician. The special safety requirements specified

in VDE 0110 v. § 49 DA/6 and VDE 0100, Part 703/11.92 §

4 must be observed during electrical installation.

l

The sauna heating and control units may be used only

in sauna cabins constructed of suitable, resin-free,

untreated material (e.g. Nordic spruce).

l

The sauna cabin must have a minimum inside height

of 2.10 m.

l

Only one sauna heater providing the required heating

output may be installed in the sauna cabin (see Table 1).

l

Every sauna cabin must have a fresh-air inlet and an

exhaust outlet. All ventilation inlets/outlets must be

positioned behind the sauna heating unit and approx.

5-10  cm  above  the  floor.  Minimum  inlet/outlet

dimensions are listed in Table 2.

l

The exhaust outlet must be positioned in the lower

section of the rear wall of the sauna cabin, diagonally

opposite the sauna heating unit. Fresh-air inlets and

exhaust outlets must not be closed. Please observe

the instructions provided by your sauna cabin supplier.

l

Caution:

 

Covered or improperly filled stone grates can

cause fire hazards.
Please ensure that no objects have been left lying on

the sauna heating unit prior to each operation.

l

Caution:

 Due to the high temperatures generated

during  operation  of  the  sauna  heating  unit,  direct

contact with the unit can cause burns.

l

The sauna heating unit is not designed for installation/

use in a niche, beneath the reclining bench or beneath

an inclined ceiling.

l

The sauna heating unit must not be operated when the

fresh-air inlet is closed.

l

Cabin lighting and lighting installation components

must be splash-resistant and suitable for operation at

environmental temperatures of up to 140

°

C. Therefore,

only VDE-tested sauna lighting systems (max. 40 Watt)

may be used in connection with the sauna heating

unit.

l

The complete sauna system (sauna heating unit,

control unit, lighting system, etc.) may be connected

to  the  main  power  system  by  a  locally  certified

electrician only. 

All electrical wiring installed inside the

cabin  must  be  suitable  for  use  at  environmental

temperatures  of  up  to  140

°

  C.  Silicone  cables  are

recommended. If single filament cables are used, they

must be protected with flexible metal tubing. Minimum

diameters for connection cables and suitable cabin

sizes for specific heating output values in kW are listed

in Table 1.

l

When installing the sauna heater, please ensure that

the vertical height between the top surface of the sauna

heater and the roof of the sauna is at least 130 cm, and

that the horizontal separation between the heater and

the cabin wall or other flammable materials is at least

10 cm. Ensure that the heater is not placed on a floor

made from highly flammable materials (e.g. wood,

plastic  flooring).  Ceramic  tiles  or  similar  are  most

suitable for the sauna area.

l

The distance between the heater guard and/or bench

and other flammable materials must be at least 10 cm.

The height of the heater  guard must be the same as

the height of the front of the stove.

l

To be used with all EOS sauna control units suitable for

additional power control units.

100 cm

(75 cm)

10 cm

80 cm

minimum 130 cm

10 cm

43 cm

10 cm

15,0

18,0

21,0

24,0

27,0

30,0

36,0

Power input

in kW

Minimum dimensions of

fresh-air inlets and exhaust

outlets in cm *)

Table 2

50 x  6 cm

50 x  6 cm

50 x  8 cm

50 x  8 cm

50 x  9 cm

50 x 10 cm

50 x 10 cm

* oder nach Angabe des Kabinenherstellers

Содержание 34.G Series

Страница 1: ...10 12 15 18 21 24 27 30 36 4 4 6 6 8 7 10 9 14 14 18 18 25 24 30 24 34 35 40 40 50 50 65 65 75 Heiz leistung in kW Anschluss an 400V 3N AC Absicherung A 3 x 25 3 x 35 3 x 50 3 x 63 Mindestquerschnitt...

Страница 2: ...der Bank oder unter ei ner Dachschr ge bestimmt l Das Saunaheizger t nicht bei geschlossener Luftein tritts ffnung in Betrieb nehmen l Die Kabinenbeleuchtung mit der dazugeh renden In stallation muss...

Страница 3: ...s Saunaheizger t und das Steuerger t aufeinander abgestimmt sind Beachten Sie die Angaben und Informationen Ihres Sau na Lieferanten Die Saunaheizger te erw rmen Ihre Saunakabine durch aufgeheizte Kon...

Страница 4: ...ger t LSG 18 90 7372 00 Sicherheitssch tz N N Sicherheitssch tz 5 x 1 5 2 x 1 5 5 x 2 5 5 x 6 Abzweigkasten Netzschalter 3 x 16 A 12 16 kW 4 18 21 kW 6 24 27 kW 10 L1 L2 L3 N L3 L2 L1 Sauna Steuerger...

Страница 5: ...Anschlusspl ne 5...

Страница 6: ...ca alle 6 Wochen damit sich die Heizst be nicht mit Feuchte anreichern k nnen F r den ordnungsgem en Anschluss der Heizger te ist der Elektroinstallateur verantwortlich und somit ist eine Haftung dur...

Страница 7: ...5 x 4 5 x 6 5 x 10 min 5 x 10 12 15 18 21 24 27 30 36 4 4 6 6 8 7 10 9 14 14 18 18 25 24 30 24 34 35 40 40 50 50 65 65 75 Heat output in kW Connection to 400 V 3N AC FuseA 3 x 25 3 x 35 3 x 50 3 x 63...

Страница 8: ...ct with the unit can cause burns l The sauna heating unit is not designed for installation use in a niche beneath the reclining bench or beneath an inclined ceiling l The sauna heating unit must not b...

Страница 9: ...haust system the sauna heater and the control unit are designed and set to work efficiently in combination Please observe the instructions and information provided by your sauna supplier Saunaheatingu...

Страница 10: ...ol unit LSG 18 90 7372 00 safety contactor N N safety contactor 5 x 1 5 2 x 1 5 5 x 2 5 5 x 6 junction box Mains switch 3 x 16 A 12 16 kW 4 18 21 kW 6 24 27 kW 10 L1 L2 L3 N L3 L2 L1 Sauna Steuerger t...

Страница 11: ...ontrol unit to 18 kW control unit 5 x 1 52 5 x 42 36 kW 3 0 kW N PE 4 3 2 1 V W U PE U 4 3 2 1 W N V 5 5 3 0 kW 3 0 kW 3 0 kW 3 0 kW 3 0 kW 3 0 kW 3 0 kW 3 0 kW 3 0 kW 3 0 kW 3 0 kW 3 0 kW 3 0 kW 3 0...

Страница 12: ...is not going to be used for a long period we recommend that it is heated up about every 6 weeks so that the heating rods do not attract moisture The electrician is responsible for connecting the heat...

Страница 13: ...13...

Страница 14: ...14...

Отзывы: