Aquablend 2500 Thermostatic Mixing Valve
Call 1300 369 273
www.enware.com
Recommended Pressures & Temperatures
MIXED OUTLET TEMPERATURE
Temperature Adjustment Range
35°-50°Celsius
INLET TEMPERATURES
Cold Supply
Minimum
5° Celsius
Maximum
30° Celsius
Hot Supply
Minimum
55° Celsius
Maximum
90° Celsius
Hot to Mix Temperatures
Differential for Stable
Operation
Minimum
10° Celsius
Cold to Mix Temperatures
Differential for Stable
Operation
Minimum
5° Celsius
FLOW RATES
To ensure stable outlet
conditions
Minimum
6 litres/minute
Maximum
85 litres/minute
DYNAMIC INLET PRESSURES
Hot & Cold Inlet Pressures
Minimum
10kPa
Maximum
500kPa
STATIC INLET PRESSURES
Hot & Cold Inlet Pressures
Maximum
1000kPa
INLET PRESSURE RATIO
Maximum inlet pressure ratio for stable
operation. (Hot : Cold or Cold : Hot)
5:1 (either
supply)
NOTE: For optimum operation it is recommended that the hot & cold
water supply pressures be balanced to /- 10%
.
NOTE: Notwithstanding the above, compliance with AS3500
must be
maintained.