FIFTH STAGE - Fitting the inline filter

Filter location

 - The filter should be located in the supply airflow between the external input point and the unit. It is 

recommended that it is fitted directly to the ECO

2

 Loft Unit spigot in a section of Ø150mm x 350mm (min) ridged 

duct. See Fig.4.

Filter Orientation

 - The cone filter should always point towards ECO

2

 Air Twin and ECO

2

 Loftight Twin.

Fixing and sealing

 - The filter should be fully sealed into the ducting, however it should not be permanently bonded 

into position, this is to allow for removal of the filter during maintenance. Use a flexible section as shown in Fig 1 & 

Fig 4 to aid removal, 300mm is recommended. Always apply the label provided to the filter location, this is to assist 

future filter maintenance (Fig 3).

Installation configurations -

 For sample configurations see (Fig 2).

Содержание ECO2 Air Twin

Страница 1: ......

Страница 2: ......

Страница 3: ...erly i e for the life of the building If the unit is mishandled you might break it This invalidates the warranty And remember if you have any problems please call our dedicated Technical Team We are a...

Страница 4: ...ECOMMENDATIONS All wiring must comply with Building Regulations and the current I E E Wiring Regulations BS7671 or the equivalent standards for your country The final installation should be examined a...

Страница 5: ...fuse 230V A C 3 core mains lead For fixing instructions please refer to the fixing instructions figure 1 on page 5 650mm x 50mm x 25mm batten Ceiling joists Contents for unit 1 x Cardboard template 2...

Страница 6: ...the diagram below ECO2 Air Twin only Fig 1 Fixing Instructions FIRST STAGE Position a dustsheet beneath the site you have chosen for cutting the hole for the diffuser Protect your lungs with a mask E...

Страница 7: ...mm x 350mm min ridged duct See Fig 4 Filter Orientation The cone filter should always point towards ECO2 Air Twin and ECO2 Loftight Twin Fixing and sealing The filter should be fully sealed into the d...

Страница 8: ...ntenance For maximum efficiency of the unit it is recommended that the filter is cleaned every 24 to 36 months by a competent person Use a vacuum cleaner a soft brush or warm water air dry fully befor...

Страница 9: ...lled by a competent person and should be connected to an electrical supply in accordance with the current electrical regulations A disconnection device should be used in the fixed wiring Connect the h...

Страница 10: ...on constant for a few seconds Next press moves the unit to the next speed and so on When the speed is chosen the LED remains on for a few seconds If the two LEDs situated just above the button flash...

Страница 11: ......

Страница 12: ...n co uk E OE MKT ENV248 V3 28 03 14 Due to our policy of continuous innovation and improvement EnviroVent reserves the right to alter products specification and appearance without notice AFTER INSTALL...

Отзывы: