IM, 

O&M Instructions – Heat Pump  

10.3

 

Refrigerant Piping 

 

ALWAYS 

 

Consult the Toshiba Installation manual before commencing installation of the outside unit and refrigerant 
pipe work. If in doubt contact 

Toshiba 24 hour Technical Helpline 0870 843 0333

 

 

 

Ensure that all refrigerant pipe is secured correctly, is within maximum pipe separation limits and is 
correctly insulated. Do not operate the outdoor unit until the system is fully commissioned. Operating the 
outdoor unit with the refrigerant circuit incomplete could cause damage to the unit. 

 

 

When the door curtain has been installed or relocated, please ensure that the refrigerant circuit is pressure 
tested and evacuated in accordance with Toshiba installation instructions and F-Gas Regulations. Failure to 
adhere to correct installation practice could lead to a system malfunction, inefficient operation and a 
breach of F-Gas Regulations relating to HFC refrigerants. 
 

 

Ensure that Oxygen Free Nitrogen gas is used to perform the pressure/leak test. 

 
 

10.4

 

Electrical Installation 

 

ALWAYS 

 

Ensure that the installer is suitably trained or qualified to carry out the electrical installation and that they 
have the appropriate personal protective equipment (PPE) and mechanical lifting aids available to allow for 
a safe installation. Only a qualified installer or qualified service person is allowed to carry out the electrical 
work on this equipment. Under no circumstances must this work be done by an unqualified individual since 
failure to carry out the work properly may result in electric shocks and /or electrical leaks. 

 

 

When connecting electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear 
gloves to provide protection for electricians and from heat, insulation shoes and clothing to provide 
protection from electric shocks. Failure to wear PPE may result in electric shocks. 
 

 

Use wiring that meets the specification in the Installation Manual and the stipulations in the local 
regulations and laws. Use of wiring that does not meet the specification may give rise to electric shocks, 
electrical leakage, smoking and/or a fire. 
 

 

Ensure you have read and understood the wiring diagram supplied with the unit. 

 

 

Ensure that a suitable fused isolated and earthed power supply is available at a maximum distance of 1.9m 
from the service level of the unit. (not Supplied) 

 

 

Check that all the components referred to in the wiring diagram are present. 

 

 

Use a suitable cable entry point or drill hole in the case using a hole saw sized to suit the cable gland being 
careful not to drop swarf inside unit or damage internal components. Any damage to an internal 
component during installation may void warranty. 

 

 

Ensure an isolator switch and circuit breaker (not supplied) that meets the specifications in the installation 
manual and the stipulation in the local regulations and laws must be installed between unit and power 
supply. 

 

 

Ensure that the unit is connected to earth (Grounding work). Incomplete grounding causes an electric 
shock. 

 

 

Check that after installation, repair or relocation that the ground wires are connected properly. 

  

 

Make sure ALL connections are tight and free from damage. 

Содержание ES D15-HP

Страница 1: ...High Wycombe Bucks HP12 3BX Tel 01494 525 342 Web www envirotec co uk Unit Type ES Type D15 HP RAV SP1104AT E Unit Type ES Type D15 HP RAV SP1104AT E_2016v1 Installation Operation Maintenance Manual...

Страница 2: ...t available to order 9 9 0 Filter Specification and Size 9 10 0 Installation 10 11 0 Operation 14 12 0 Wiring Schematics 15 13 0 Commissioning 18 13 0 Troubleshooting 18 14 0 Service Maintenance Instr...

Страница 3: ...ally hazardous When handling operating or carrying out maintenance on the unit personnel must use safe engineering practices and observe all relevant local health and safety requirements and regulatio...

Страница 4: ...used ladders towers etc are isolated from passing human traffic by the use of an appropriate barrier notice system Any barriers used should be positioned at a suitable distance to remove risk of injur...

Страница 5: ...ow the installation instructions carefully to ensure correct and safe installation of the product Enviroscreen ES Type D Free hanging via drop rods front access to air intake filter Maintenance via fr...

Страница 6: ...V SP1104AT E Heating Capacity kW 2 4 13 0 Heating Power Input kW 2 52 Operating Range Cooling Heating C 43 to 15 15 to 15 Standard Air Flow l s 1683 Standard Air Flow m3 h 6060 Sound Pressure Level Co...

Страница 7: ...S D 15 1500 1470 87 1 0 184 2 5 7 5 0 63 11 20 A 317 340 B Plan View 46 160 53 225 72 29 1 x 20mm 1 x 25mm Coil connections 22mm plain copper tails Cable Entry Points Enviroscreen Type ES D Fixing det...

Страница 8: ...25 Mounting bolt hole 12 17 long hole Mounting bolt hole 12 17 U shape hole B legs Details of A legs Details of B legs A legs 55 95 2 1 64 1 65 7 83 7 Knockout for downward piping Z views 655 121 534...

Страница 9: ...ower Input kW Maximum Operating Current Amp ES 15 SM1104AT E TO 2 8900 I1 SVB CC05 1 3 1 14 4 For isolator sales contact Envirotec on 01494 525342 or sales envirotec co uk quoting model number and ser...

Страница 10: ...Check the unit will cover the full width of the door with minimum 100mm overlap each side Mount the unit as close to the door as possible Note that the maximum mounting height dimension is from fixed...

Страница 11: ...ids available to allow for a safe installation Remove front panel by removing fixing screws to access fixing points Replace screws into holes for safe keeping during installation Make sure that the fi...

Страница 12: ...ince failure to carry out the work properly may result in electric shocks and or electrical leaks When connecting electrical wires repairing the electrical parts or undertaking other electrical jobs w...

Страница 13: ...Megger to check the resistance is 2M or more between the charge section and the non charge metal section Earth section If the resistance value is low a disaster such as a leak or electric shock is cau...

Страница 14: ...eaker and contact a qualified service person Fan Speed button 1 Select Fan speed by pressing 1 Unit may be single speed only If this is the case then this button will have no use Adjust the desired se...

Страница 15: ...earth screw 2 Pole Isolator L1 N 220 240V AC Single Phase Neutral Earth RAV SM1104AT8 E 3 Pole Isolator All A B wiring to be 2 Core Twisted Screened 220 220V AC Single Phase 3 Core Earth BMS Input Dev...

Страница 16: ...urtain earth screw Outdoor Unit earth screw 2 Pole Isolator L1 N 220 240V AC Single Phase Neutral Earth RAV SM1104AT8 E 3 Pole Isolator All A B wiring to be 2 Core Twisted Screened 220 220V AC Single...

Страница 17: ...Door Curtain 1 Remote Control RBC AS41E A B A B All A B wiring to be 2 Core Twisted Screened BMS Input Device Optional Extra Envirotec Drawing Ref GSS1124 Master Slave Door Curtain 2 A B Door Curtain...

Страница 18: ...electrical terminations tight Control panel Switch and unit Checks with power applied Only undertake these test once all covers have been refitted and unit is electrically safe Fan speeds correct if...

Страница 19: ...g diagram is available Climb onto or place objects on top of the door curtain You may fall or objects may fall off and result in injury 14 2 Service ALWAYS Inspect for mechanical and electrical defect...

Страница 20: ...is available This will avoid costly damage 14 7 Washable filters where fitted ALWAYS Inspect the unit after is has been running for two weeks to establish a time scale within which the filters should...

Страница 21: ...Type B Unit Type C Toshiba ES Type with RAV Super Digital Inverter Heat Pump Remark the installer is obligated to ensure that all of the heating system complies with the PED directive If modifications...

Страница 22: ...EQYLURWHF WG HVERURXJK 3DUN 5RDG LJK FRPEH XFNLQJKDPVKLUH 3 DOO PDLO IUHVKWKLQNLQJ HQYLURWHF FR XN...

Отзывы: