background image

EP-2000 Series  INSTALLATION GUIDE

6

Mounting

For  optimal  performance,  mount  EP  product  as  close  to 
electrical panel as possible. Longer wire increases inductance 
in  the  system  and  the  EP  unit  may  not  function  properly. 
Make  sure  the  EP  product  is  mounted  in  a  dry  and  clean 
environment. The EP unit can be mounted in any secure area 
above, below, beside or inside the electrical panel.

 
For optimal performance: 

• 

EP-2000 should be connected no more than 6  inches 
from electrical panel.

• 

EP-2500 should be connected no more than 12 inches 
from electrical panel.

Although internal mounting can be preferred mounting for 
shorter lead lengths and optimal performance, it poses two 
problems: 

1. 

IEEE  does  not  recommend  internal  mounting  of 
Waveform  Corrector  in  the  event  of  end  of  life 
termination of the unit that may cause damage to the 
internal distribution panel. 

2. 

On  internal  installation  the  panel  must  be  opened  for 
visual verification of units’ functional status.  

 
Ensure  you  have  considered  all  of  these  options  before 
attempting internal installation.

WARNING

• 

ALWAYS have a professional  

electrician with proper safety 

equipment perform installation. 

• 

Any attempt to open unit voids  

warranty.

!

!

SIDE MOUNTING

EP  units  are  designed  for  installation  to  ½  inch 
panel knockout on side, top or bottom of panel. 
Unit may also be secured with #8 self tapping or 
wood screws. 

 

INTERNAL MOUNTING

Ensure  a  minimum  of  1  inch  clearance  to  all 
electrical surfaces before attempting an internal 
mounting.

  

Отзывы: