EP-2000 Series  INSTALLATION GUIDE

4

Voltage Ratings  &  Power Source Configurations

Single Leg 1 Wire, 1 N Ground Installation

 
 
 
 

1. 

Connect white neutral to neutral bus bar. 

2. 

Next connect black phase A to phase A of the 30 A breaker. 

3. 

Last connect green ground to ground bus bar or panel. Ground is case ground only 
and should NOT be connected to neutral bus bar. 

SINGLE PHASE WYE

PRODUCTS

EP-2000 
EP-2050
EP-2500 
EP-2550

VOLTAGE 

ID#

MCOV

1L120

132 V

1L290

264 V

Single Phase Installation

 
 
 
 

1. 

Connect white neutral to neutral bus bar. 

2. 

Next connect black phase A to phase A of the 30 A breaker. 

3. 

Then connect black phase B to phase B of 30 A breaker.

4. 

Last connect green ground to ground bus bar or panel. Ground is case ground only 
and should NOT be connected to neutral bus bar. 

TWO PHASE WYE

PRODUCTS

EP-2000 
EP-2050
EP-2500 
EP-2550

VOLTAGE 

ID#

MCOV

1S240

132 V

Three Phase Wye Installation

 
 
 
 

1. 

Connect white neutral to neutral bus bar. 

2. 

Next connect black phase A to phase A of the 30 A breaker. 

3. 

Then connect black phase B to phase B of 30 A breaker.

4. 

Then connect black phase C to phase C of 30 A breaker. 

5. 

Last connect green ground to ground bus bar or panel. Ground is case ground only 
and should NOT be connected to neutral bus bar. 

THREE PHASE WYE

PRODUCTS

EP-2000
EP-2500 

VOLTAGE 

ID#

MCOV

3Y208

132 V

3Y240

132V

3Y480

304V

3Y600

380V

L

N

Single Phase 1 Wire + Neutral

L1

N

L2

Split Phase 2 Wire + Neutral

L1

N
L2

L3

3 Phase Wye 3 Wire + Neutral

single leg 1 wire + 1 neutral

single phase, 2 wire + 1 neutral

3 phase Wye, 3 wire + 1 neutral