Enviromaster CHP Скачать руководство пользователя страница 5

www.enviromaster.com

The Ductless Split System of Choice

5

As of 12/01/04, the 24V control transformer is located in 

the air handler unit. 

This provides low volt control power 

to both the air handler and condenser. Depending on the 

models selected, the 

low Volt

 interconnect control wiring 

may be effected. 

Note: All low volt interconnect wiring must be at 

least 18 awg.

  

COOLING ONLY UNITS 

With or Without Heat

Cooling only units utilize two 

low Volt

 interconnecting wires 

between the indoor and outdoor units. Wires (WCP/WHP) 

or terminals (CCP/CHP/FCP/FHP) designated “Y” (yellow) 

and “C” (brown) of the air handler should be connected to 

the corresponding “Y” (yellow) and “C” (brown) wires or 

terminals of the condenser. Other wires or terminals such 

as “R” (red) or “O” (orange) may not be needed and should 

be protected by a wire nut from making contact with the 

junction box or other metal surfaces.

Refer to low Volt interconnect diagram interconnect diagram 

Figure 1

 for unit mounted controls.

HEAT PUMP CONNECTION - UNIT MOUNT 

CONTROLS Two-Stage Heating

When  connecting  to  a  defrosting  heat  pump,  such  as 

EMI model SHC, indoor units with electric heat utilize five 

interconnecting 

low  Volt

  wires  between  the  indoor  and 

outdoor units. When connecting to limited range heat pumps 

such as EMI models MH2 and MH4 

built after 12/01/04

indoor units with electric heat utilize four interconnecting 

low Volt wires. In this case the “R” (red) may not be needed 

and should be protected by a wire nut from making contact 

with the junction box or other metal surfaces.

LOW VOLT INTERCONNECT WIRING FOR UNIT MOUNTED CONTROLS

In  addition  to  the  “Y”  and  “C”  connections  required  for 

cooling, heat pumps require a reversing valve control wire 

“O” (orange) that is energized in the cooling mode. If the 

indoor unit has an electric heater then a ”W” (white) wire 

connection  may  also  be  needed  to  energize  the  indoor 

electric  heat.  Heat  pumps  models  SHC  require  an  “R” 

connection between the indoor and outdoor unit to provide 

power  to  the  defrost  control  board  in  the  condenser. 

Heat pump models MH2 and MH4 do not require an “R” 

connection 

after 12/01/04

 since the transformer is located 

in the air handler.

Note: 

Two-stage heating requires the combination of a 

heat pump condenser and an indoor unit that is equipped 

with an electric strip heater. The indoor electric heater 

will energize as the second stage heat source, when the 

room temperature falls by two degrees or more below the 

set point, and also during the defrost mode for models 

SHC. For limited range heat pumps models MH2 and 

MH4, heat pump operation will cease when the outdoor 

temperature falls below 35°F. In this case the electric 

strip heater will remain sole heat source.

Refer to low Volt interconnect diagram interconnect diagram 

Figure 1

 for unit mounted controls.

REMOTE THERMOSTAT CONTROLS

As of 12/01/04, the 24V control transformer is located in 

the air handler unit. 

This provides low volt control power 

to both the air handler and condenser. Depending on the 

models selected, the interconnect control wiring may be 

effected.

Note: All

 low Volt

 interconnect wiring must be at 

least 18 awg.

Choosing  a  Remote  Wall  Mounted  Thermostat: 

See 

“Wall Thermostat Control” section Pg. 21-22

Figure 1

COMMON TO ALL AIR HANDLERS 

Continued

Содержание CHP

Страница 1: ...NCE MANUAL EMI DUCTLESS SPLIT SYSTEM AIR HANDLERS FLOOR MODEL AIR HANDLER FCP FHP WALL MOUNTED AIR HANDLER WCP WHP CEILING MOUNTED AIR HANDLER CHP An ISO 9001 2000 Certi ed Company Enviromaster Intern...

Страница 2: ...lting in re electrical shock property damage personal injury or death TO THE INSTALLER 1 Retain this manual and warranty for future refer ence 2 Before leaving the premises review this manual to be su...

Страница 3: ...ring 18 awg required High voltage power supply wiring Mounting fasteners screws wall anchors etc Chilled water condensate and refrigerant piping Refrigerant for interconnect charge Hot water piping Fl...

Страница 4: ...unit The cabinet service panels must be able to be removed without obstruction FCP FHP CCP CHP units can be equipped with hot water coil Unit mount control panel standard on FHP FCP and WHP WCP optio...

Страница 5: ...l surfaces LOW VOLT INTERCONNECT WIRING FOR UNIT MOUNTED CONTROLS In addition to the Y and C connections required for cooling heat pumps require a reversing valve control wire O orange that is energiz...

Страница 6: ...Heat pump operation requires the connection of the O orange terminal from the outdoor unit to the thermostat The reversing valve is energized in the cooling mode for EMI models SHC heat pump condenser...

Страница 7: ...according to the table below Figure 4 FHP FCP to gain access to the relay board rst remove the return air grill from the bottom front of the unit The relay board is located in the control section Set...

Страница 8: ...for mounting the unit for optimum air circulation 3 Locate the indoor and outdoor units as close together as possible See outdoor unit requirements UNIT MOUNTING The FHP FCP is designed to sit direct...

Страница 9: ...FRIGERANT PIPING The FHP is equipped with a Flo Rater Piston Expan sion Device Connections are male are type are nuts not included The suction line large must be insulated the entire length with close...

Страница 10: ...DIMENSIONS AND SPECIFICATIONS NOTE Due to ongoing development programs design and speci cations may change without notice FCP PIPING SPECIFICATIONS Model Chilled Water Line Size Supply Return Drain H...

Страница 11: ...om FHP Electric Heat Speci cations table 36 requires piston kit 550 121 see pg 5 FCP FHP ELECTRICAL HEAT SPECIFICATIONS Model Voltage KW Heater Amps Total Amps Min Circuit Amps Max Fuse Amps 9 12 15 2...

Страница 12: ...torized Damper and Power Assisted Fresh Air 2 Fan Type Wall Box Dimensions 14 from nished oor level x 17 wide x 8 deep Model Air Handler Condenser Btuh Factory Installed Field Changeover Part Piston O...

Страница 13: ...Use the cardboard template provided with unit packing to test t the unit before installation 1 The CHP Series is designed to be mounted to a horizontal surface which should be plumb and level 2 Using...

Страница 14: ...3 4 Flare nuts not included CHP WITH ELECTRIC HEAT OPTIONS Model Voltage KW Htr Amps Total Amps Min Cir Amps Max Fuse 12 208 230 3 13 1 13 7 17 1 20 18 24 208 230 5 21 7 22 8 28 6 30 CHP ELECTRICAL SP...

Страница 15: ...rom unit Determine if the cabinet front can be removed with out obstruction WALL MOUNTED AIR HANDLER WCP WHP NOTE Please refer to the Common section in the front of this manual for more detailes on Co...

Страница 16: ...Factory Installed Field Replacement Part Piston Ori ce Piston Ori ce Size Part Piston Ori ce Piston Ori ce Size WHP12 9 000 240 4064 044 240 727 041 12 000 NO CHANGE WHP18 15 000 240 4111 053 240 101...

Страница 17: ...21 7 22 3 27 9 30 36 230 5 21 7 22 3 27 9 30 WCP CAPACITIES Model Nominal Capacaties Total Capacity Sensible Capacity Fluid Temp Fluid Flow PD Ft H2 0 09 12 9 000 7 375 6 732 45 1 0 8 10 801 8 272 45...

Страница 18: ...is designed to optimize system performance and protect the refrigeration system from unwanted short cycling and evaporator freeze ups Operation of the unit can be made by either the keypad on the uni...

Страница 19: ...ton Select Cool mode via the Mode button The room temperature will be displayed Then by depressing either the Up or Down arrow once the setpoint temperature will appear The setpoint temperature can th...

Страница 20: ...tpoint temperature will appear The setpoint temperature can then be changed with each successive press of the Up or Down arrow or by holding the button in Placethesetpointtemperatureatadesiredroomtemp...

Страница 21: ...quipped with an auto on fan switch When this switch is placed in the on position the indoor fan will run continuous When the switch is in the auto position the indoor fan will cycle with the call for...

Страница 22: ...system or from abnormally cold air from the evaporator coil Should the freeze sensor activate the indoor fan will switch off to eliminate the source of cold fresh air and also the outdoor condensing...

Страница 23: ...l Number Technician Serial Number Mode Cooling Indoor Section Notes Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving Air WB Outdoor Section Entering A...

Страница 24: ...ailure to do so could result in physical injury and or electrical shock When trouble shooting the indoor unit please refer to the wiring diagram that is supplied with the equipment It is located eithe...

Страница 25: ...mote thermostat connection A 24V transformer located in the indoor air handler unit as of 12 01 04 provides low Volt control power to both the indoor air handler and outdoor condenser The 24V power su...

Страница 26: ...eversing valve will not be energized To check for a condenser signal place the indoor unit or wall thermostat in heating Next place the set point temperature one degree above room temperature to call...

Страница 27: ...ce all circuit boards including the unit keypad Do not attempt to trouble shoot the individual circuit boards Q The display tends to icker at times Is this normal A A small amount of ickering of the d...

Страница 28: ...or application by others Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs nee...

Отзывы: